Plan Review Notes
Plan Review Notes For Permit 19031377
Permit Number 19031377
Review Stop B
Sequence Number 1
Notes
Date Text
2019-04-15 14:59:44BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. PROVIDE SITE DRAINAGE PLAN.
 FBC R401.3 SITE DRAINAGE
 PROVIDE TWO SETS OF A SITE DRAINAGE PLAN SHOWING
 COMPLIANCE WITH FBC R401.3 DRAINAGE.
 SURFACE DRAINAGE SHALL BE DIVERTED TO A STORM SEWER
 CONVEYANCE OR OTHER APPROVED POINT OF COLLECTION THAT
 DOES NOT CREATE A HAZARD.
 LOTS SHALL BE GRADED TO DRAIN SURFACE WATER AWAY FROM
 FOUNDATION WALLS. THE GRADE SHALL FALL A MINIMUM OF 6
 INCHES WITHIN THE FIRST 10 FEET.
 EXCEPTION: WHERE LOT LINES, WALLS, SLOPES OR OTHER
 PHYSICAL BARRIERS PROHIBIT 6 INCHES OF FALL WITHIN 10
 FEET, DRAINS OR SWALES SHALL BE CONSTRUCTED TO ENSURE
 DRAINAGE AWAY FROM THE STRUCTURE.
 IMPERVIOUS SURFACES WITHIN 10 FEET OF THE BUILDING
 FOUNDATION SHALL BE SLOPED A MINIMUM OF
 2 PERCENT AWAY FROM THE BUILDING.
  
 2. PALM BEACH COUNTY IMPACT FEES REQUIRED.
 PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL
 (561) 233-5025. UPON APPROVAL, YOU MAY CHECK OUT ONE
 PLAN SET AND TAKE TO THAT OFFICE FOR REVIEW. PLEASE
 RETURN STAMPED AND WITH A COPY OF THE RECEIPT AS
 APPLICABLE. PLEASE PROVIDE THE MUNICIPAL IMPACT FEE
 QUESTIONNAIRE FORM TO THE PBC IMPACT FEE OFFICE. THE
 FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/AD
 MINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF
  
 3. ROOFING PERMIT REQUIRED. FBC 105 PERMITS
  
 4. PROVIDE WINDOW AND DOOR SCHEDULE.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 5. PROVIDE DESIGN PRESSURES FOR WINDOW AND DOOR
 OPENINGS.
 FBC 107.3.5.3 ? PROVIDE WIND DESIGN LOADS/DESIGN
 PRESSURES PURSUANT TO FBC-R301.2.
  
 R301.2.1 WIND DESIGN CRITERIA.
 BUILDINGS AND PORTIONS THEREOF SHALL BE CONSTRUCTED IN
 ACCORDANCE WITH THE WIND PROVISIONS OF THIS CODE USING
 THE BASIC WIND SPEED IN TABLE R301.2(1) AS DETERMINED
 FROM FIGURE R301.2(4). THE STRUCTURAL PROVISIONS OF
 THIS CODE FOR WIND LOADS ARE NOT PERMITTED WHERE WIND
 DESIGN IS REQUIRED AS SPECIFIED IN SECTION R301.2.1.1.
 WHERE DIFFERENT CONSTRUCTION METHODS AND STRUCTURAL
 MATERIALS ARE USED FOR VARIOUS PORTIONS OF A BUILDING,
 THE APPLICABLE REQUIREMENTS OF THIS SECTION FOR EACH
 PORTION SHALL APPLY. WHERE NOT OTHERWISE SPECIFIED, THE
 WIND LOADS LISTED IN TABLE R301.2(2) ADJUSTED FOR
 HEIGHT AND EXPOSURE USING TABLE R301.2(3) SHALL BE USED
 TO DETERMINE DESIGN LOAD PERFORMANCE REQUIREMENTS FOR
 WALL COVERINGS, CURTAIN WALLS, ROOF COVERINGS, EXTERIOR
 WINDOWS, SKYLIGHTS AND EXTERIOR DOORS (OTHER THAN
 GARAGE DOORS).
  
 6. SHOW LOCATION AND TYPE OF WATER HEATER ON PLAN.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED.
  
  