2020-11-05 13:10:21CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 NFPA 54 = NATIONAL FUEL GAS CODE
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 SEE RECORD DRAWING MASTER PERMIT 18060100
  
 4TH REVIEW
 GAS COMMENTS:
  
  
 1.SUBMITTED GAS ISOMETRIC AND LOCATION PLAN SHOWS
 COOKTOP AT 57,000 BTUH. SUBMITTED SPECS-GAS OVEN HAS A
 TOTAL OF 83,000 BTUH
  
 2.TOTAL BTUH ON SUBMITTED PLAN IS 115,500. TOTAL IS
 ACTUALLY 141,500 BTUH.
  
 3.RISER DIAGRAM AND SIZING TABLES ONLY INDICATE PE
 PIPING WHICH IS THE UNDERGROUND. TRANSITION TO ABOVE
 GROUND AND CONNECTION PIPING SHALL COMPLY WITH FBC FG
 404.17.1 (PREMANUFACTURED ANODELESS RISERS OR SERVICE
 HEAD ADAPTER RISERS); PROVIDE MATERIAL SPEC AND SIZING
 TABLE FOR PIPING FROM SHUTOFF VALVE TO APPLIANCE.
  
 4.PROVIDE NOTE "INSTALL TRACER WIRE COMPLYING WITH FBC
 FG 404.17.3."
  
 5.REGARDING PREVIOUS REQUESTS FOR COMBUSTION AIR
 CALCULATIONS: SUBMITTED FLOOR PLAN DOES NOT CORRECTLY
 REFLECT RECORD DRAWING DIMENSIONS FOR THE
 KIT/LIVING/DINING. SUBMITTED PLAN FOR KIT/LIVING/DINING
 = ?18? FT X 14 FT 8 IN X 10 FT=2,640.6 CU FT
 RECORD PERMIT PLAN 18060100 INDICATES 10 FT CEILING
 HEIGHTS FOR THE AFFECTED ROOMS. YOU SHOULD REFER TO
 RECORD DRAWING MASTER PERMIT 18060100 PLAN SHEET A.2
 WHEN SUBMITTING CALCULATIONS.
 KIT/LIVING/DINING = 16 FT X 14 FT 8 IN X 10 FT=2,347.2
 CU FT
 FOYER=3 FT X 5 FT 9 IN X 10 FT=530.6 CU FT
 HALL=7 FT 7 IN X 5 FT 9 IN =172.5 CU FT
 TOTAL AVAILABLE COMBUSTION AIR =3,050.3 CU FT; REQUIRED
 IS 4,150 CU. FT. SEE BELOW
 SUBMITTED RANGE BTUH
 UPPER OVEN = 14,500 BTUH
 LOWER OVEN = 14,000 BTUH
 LR BURNER = 9,000 BTUH
 RR BURNER = 5,000 BTUH
 LF BURNER = 12,000 BTUH
 RF BURNER = 18,500 BTUH
 CENTER WARMER = 10,000 BTUH
 TOTAL APPLIANCE = 83,000 BTUH
 TOTAL COMBUSTION AIR REQUIRED CALCULATING PER FBC FG
 304.5.1 IS 4,150 CU FT.
  
 6. AS PREVIOUSLY NOTED, A REVISION SHALL BE IN PLACE
 FOR THE FINAL INSPECTION WHICH SHALL REMOVE THE HOOD
 VENT FROM RECORD DRAWING MASTER PERMIT 18060100 PLAN
 SHEET P.1.
  
 NOTE: PER WPB FBC 107.1, DESIGNER TO PROVIDE DIGITAL
 SIGNATURE IN ACCORDANCE WITH FAC AND FS OR SHALL
 PROVIDE WET SIGNED PAPER DOCUMEN(S)T PRIOR TO PERMIT
 ISSUANCE. CALL 561-805-6724 FOR ADDITIONAL INFORMATION.
 END OF COMMENTS.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
 ALL PLANS TO BE SIGNED AND SEALED BY THE DESIGNER AS
 REQUIRED BY FAC AND FS.
 ALL PLANS TO BE DIGITALLY SIGNED AND SEALED BY THE
 DESIGNER IN ACCORDANCE WITH FAC AND FS.
  
  
  