Plan Review Notes
Plan Review Notes For Permit 19031376
Permit Number 19031376
Review Stop G
Sequence Number 3
Notes
Date Text
2019-05-30 07:02:51GAS 3RD REVIEW**DENIED**
  
  
 1) OK
  
 2) OK
  
 3) UNDER DESCRIPTION YOU STATE YOUR ARE DELETING THE
 GAS LAMPS. SUPPLY A GAS ISOMETRIC THAT DOES NOT SHOW
 THE GAS LAMPS ON IT. FBC 107.3.5
  
 4) PROVIDE DIMENSIONS AND SHOW HOW YOU CAME UP WITH THE
 4,500 CUBIT FEET OF MAKE UP AIR. PER THE APPROVED PLAN
 I CAN NOT SEE HOW THIS WAS DONE.
  
 5) A REVISION BY FINAL INSPECTION WILL BE REQUIRED
 REMOVING THE HOOD VENT FROM THE MASTER PERMIT #
 18060100 ON SHT. P1.
  
 6) PROVIDE WHICH MODEL BBQ YOU ARE USING AS NONE OF THE
 MODEL IN THE SPEC SHEETS SHOW THE 110,000BTU CALLED OUT
 ON YOUR PLAN
  
  
 TIM HUNT
 PLUMBING PLANS EXAMINER
 BUILDING DIVISION
 CITY OF WEST PALM BEACH
 401 CLEMATIS STREET, 1ST FLOOR
 WEST PALM BEACH, FL 33401
 561-248-2703
 [email protected]
  
  