2019-05-20 08:22:37GAS 2ND REVIEW**DENIED**FL ST 553.80 (B)2B WITH RESPECT
 TO EVALUATION OF DESIGN PROFESSIONALS? DOCUMENTS, IF A
 LOCAL GOVERNMENT FINDS IT NECESSARY, IN ORDER TO
 ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING CODE AND
 ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS REQUIRED BY
 THE CODE THREE OR MORE TIMES FOR FAILURE TO CORRECT A
 CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY NOTED IN
 EACH REJECTION, INCLUDING, BUT NOT LIMITED TO, EGRESS,
 FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY,
 ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL,
 MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER
 REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING
 COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL
 GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH
 REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION,
 A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE
 PERMIT FEE ATTRIBUTED TO PLANS REVIEW.
  
  
 1) OK
  
 2) 2ND REQUEST.VALUE OF JOB SEEMS LOW. PROVIDE BONA
 FIDE SIGNED CONTRACT. COST MUST INCLUDE THE GAS STOVE
 AND GAS LIGHTS. BBQ WAS INCLUDING UNDER MASTER PERMIT #
 18060100. W.P.B AMEND FBC 109.3
  
 3) 2ND REQEST. NO INFORMAION OTHER THEN A BASIC UL
 APPROVAL SUBMITTED FOR THE GAS LIGHTS.PROVIDE COMPLETE
 INSTALLATION MANUAL WHICH MUST ALSO INCLUDE THE MODEL
 OF UNITS TO MATCH UL APPROVAL. WHICH MODEL STOVE IS
 BEING USED?.SUBMIT MANUFACTURER'S SPECIFICATION SHEETS
 / INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO VERIFY
 COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND
 FBC-2017 FUEL GAS CODE SEC. 402.2, AND 301.3 OR 2017
 FBC-RES. SEC. G2404.3. SEC.G2408.1.
  
 4) 2ND REQUEST. PROVIDE COMBUSTION AIR FOR THE STOVE.
 MASTER PERMIT #18060100 WAS APPROVED FOR ELC STOVE.
 2017 FBC-FUEL GAS SEC.304.9.3 OR FBCR G2407.9.3.
  
 5) 2ND REQUEST.PROVIDE HOOD EXHAUST VENTING DETAIL FOR
 THE BBQ AS CALLED OUT ON MASTER PERMIT # 18060100 SHT
 P1
  
 6) NEW COMMENT. SUBMIT 2 COPIES OF ALL SUBMITTAL
 DOCUMENTS. FBC 107.3.5
  