| Plan Review Notes For Permit 19031376 |
| Permit Number |
19031376 |
|
| Review Stop |
G |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2019-04-02 13:51:31 | GAS 1ST REVIEW**DENIED** | | | | | | 1) PERSON THAT DESIGNS PLAN SHALL TAKE RESPONSIBILITY | | | BY SIGN AND DATED PLAN. F.S 471 | | | | | | 2) VALUE OF JOB SEEMS LOW. PROVIDE BONA FIDE SIGNED | | | CONTRACT. COST MUST INCLUDE THE GAS STOVE AND LIGHTS. | | | BBQ WAS INCLUDING UNDER MASTER PERMIT # 18060100. W.P.B | | | AMEND FBC 109.3 | | | | | | 3) SUBMIT MANUFACTURER?S SPECIFICATION SHEETS / | | | INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO VERIFY | | | COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND | | | FBC-2017 FUEL GAS CODE SEC. 402.2, AND 301.3 OR 2017 | | | FBC-RES. SEC. G2404.3. GAS APPLIANCES SHALL BE LISTED | | | AND LABELED. THE INSTALLATION MANUALS FOR ALL GAS | | | APPLIANCES / EQUIPMENT SHALL BE ONSITE AT THE TIME OF | | | INSPECTION. FGC SEC.305.1, FBC-RES. SEC.G2408.1. | | | | | | 4) MASTER PERMIT #18060100 WAS APPROVED FOR ELC STOVE. | | | PROVIDE COMBUSTION AIR CALCULATIONS FOR THE GAS STOVE. | | | 2017 FBC-FUEL GAS SEC.304.9.3 OR FBCR G2407.9.3. | | | | | | 5) PROVIDE HOOD EXHAUST VENTING DETAIL FOR THE BBQ AS | | | CALLED OUT ON MASTER PERMIT # 18060100 SHT P1 | | | | | | TIM HUNT | | | PLUMBING PLANS EXAMINER | | | BUILDING DIVISION | | | CITY OF WEST PALM BEACH | | | 401 CLEMATIS STREET, 1ST FLOOR | | | WEST PALM BEACH, FL 33401 | | | 561-248-2703 | | | [email protected] | | | | | | | | | | | | |
|