Plan Review Notes
Plan Review Notes For Permit 19031376
Permit Number 19031376
Review Stop G
Sequence Number 1
Notes
Date Text
2019-04-02 13:51:31GAS 1ST REVIEW**DENIED**
  
 1) PERSON THAT DESIGNS PLAN SHALL TAKE RESPONSIBILITY
 BY SIGN AND DATED PLAN. F.S 471
  
 2) VALUE OF JOB SEEMS LOW. PROVIDE BONA FIDE SIGNED
 CONTRACT. COST MUST INCLUDE THE GAS STOVE AND LIGHTS.
 BBQ WAS INCLUDING UNDER MASTER PERMIT # 18060100. W.P.B
 AMEND FBC 109.3
  
 3) SUBMIT MANUFACTURER?S SPECIFICATION SHEETS /
 INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO VERIFY
 COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND
 FBC-2017 FUEL GAS CODE SEC. 402.2, AND 301.3 OR 2017
 FBC-RES. SEC. G2404.3. GAS APPLIANCES SHALL BE LISTED
 AND LABELED. THE INSTALLATION MANUALS FOR ALL GAS
 APPLIANCES / EQUIPMENT SHALL BE ONSITE AT THE TIME OF
 INSPECTION. FGC SEC.305.1, FBC-RES. SEC.G2408.1.
  
 4) MASTER PERMIT #18060100 WAS APPROVED FOR ELC STOVE.
 PROVIDE COMBUSTION AIR CALCULATIONS FOR THE GAS STOVE.
 2017 FBC-FUEL GAS SEC.304.9.3 OR FBCR G2407.9.3.
  
 5) PROVIDE HOOD EXHAUST VENTING DETAIL FOR THE BBQ AS
 CALLED OUT ON MASTER PERMIT # 18060100 SHT P1
  