2019-04-11 12:02:11APPROVED
 PROVISO
 1. SEE RED LINED COMMENTS ON P-4 SANITARY RISER DIAGRAM
 AND P-2 SECOND FLOOR PLAN REGARDING THE SECOND FLOOR
 BATHROOM, RM #201; THE TUB/SHOWER FIXTURE DRAIN SHALL
 CONNECT TO THE HORIZONTAL WET VENT, NOT INTO THE TOP OF
 THE VERTICAL SOIL STACK PER FBC RES P3108.1.
 2. PROVIDE BY DEFERRED SUBMITTAL AS ALLOWED BY WPB FBC
 107.3.4.1, MARKED UP MANUFACTURER'S SPEC SHEET, NOTING
 FULL MODEL NUMBER, AND APPLICABLE SPECIFICS PER WPB FBC
 107.2.1. SAID SUBMITTAL SHALL BE APPROVED AND IN PLACE
 PRIOR TO FIRST PLUMBING INSPECTION.
 3. SEE WATER PIPING SYSTEM NOTE #5 ON P-3. WATER HAMMER
 ARRESTORS REQUIRED FOR AUTOMATIC CLOTHES WASHER.
 3. ALL WORK PER CITY CODES SUBJECT TO FIELD INSPECTOR'S
 APPROVAL
  
2019-04-11 11:38:53APPROVED
 PROVISO
 1. SEE RED LINED COMMENTS ON P-4 SANITARY RISER DIAGRAM
 AND P-2 SECOND FLOOR PLAN REGARDING THE SECOND FLOOR
 BATHROOM, RM #201; THE TUB/SHOWER FIXTURE DRAIN SHALL
 CONNECT TO THE HORIZONTAL WET VENT, NOT INTO THE TOP OF
 THE VERTICAL SOIL STACK PER FBC RES P3108.1.
 2. PROVIDE BY DEFERRED SUBMITTAL AS ALLOWED BY WPB FBC
 107.3.4.1, MARKED UP MANUFACTURER'S SPEC SHEET, NOTING
 FULL MODEL NUMBER, AND APPLICABLE SPECIFICS PER WPB FBC
 107.2.1. SAID SUBMITTAL TO BE APPROVED AND IN PLACE
 PRIOR TO FIRST PLUMBING INSPECTION.
  
  