Plan Review Notes
Plan Review Notes For Permit 19031375
Permit Number 19031375
Review Stop G
Sequence Number 1
Notes
Date Text
2019-04-11 14:19:08CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 WPB CCC = WEST PALM BEACH CROSS CONNECTION CONTROL
 MANUAL
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
 NFPA 54=NFPA 54 2018 FUEL GAS CODE
  
 1ST REVIEW: FUEL GAS
 A SEPARATE PERMIT IS REQUIRED
  
 COMMENTS: DENIED
  
 1. GAS RISER DIAGRAM TO SHOW ALL CUT LENGTHS INCLUDING
 DROP AND BRANCHES TO RANGE AND DRYER AS WELL AS
 UNDERGROUND TO FUTURE BBQ GRILL PER FBC RES G2413.4.1,
 G2413.4.2.PLEASE
 2. PER WPB FBC 107.2.1, PROVIDE DETAIL FOR SAFEING OFF
 AND SECURING OF TERMINATION OF PIPING FOR FUTURE BBQ
 GRILL.PROVIDE NOTE AT VALVE UPSTREAM OF UNDERGROUND
 "VALVE SHALL BE PROVIDED WITH LOCK-OUT".
 3. PER WPB FBC 107.2.1 AND 107.3.5.3.13, SUBMIT
 CALCULATIONS FOR COMBUSTION AIR PER FBC RES G2407.1 AND
 G2439.4. WHERE COMBUSTION AIR IS PROVIDED BY THE
 BUILDING?S MECHANICAL VENTILATION SYSTEM, THE SYSTEM
 SHALL PROVIDE THE SPECIFIED COMBUSTION AIR RATE IN
 ADDITION TO THE REQUIRED VENTILATION AIR FBC RES
 G2407.9.3.
 4. PER WPB FBC 107.2.1 AND 107.3.5.3.13, SUBMIT
 MANUFACTURER?S SPECIFICATION SHEETS / INSTALLATION
 MANUAL FOR ALL GAS EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND FBC-2017 FUEL GAS CODE
 SEC. 402.2, AND 301.3 OR 2017 FBC-RES. SEC. G2404.3.
 GAS APPLIANCES SHALL BE LISTED AND LABELED. THE
 INSTALLATION MANUALS FOR ALL GAS APPLIANCES / EQUIPMENT
 SHALL BE ONSITE AT THE TIME OF INSPECTION. FGC
 SEC.305.1, FBC-RES. SEC.G2408.1.
 5. PER NFPA 54 7.1.7.3 - AN ELECTRICALLY CONTINUOUS
 CORROSION-RESISTANT TRACER WIRE SUITABLE FOR DIRECT
 BURIAL (MINIMUM AWG 14) OR PRODUCT SPECIFICALLY
 DESIGNED FOR THAT PURPOSE, SHALL BE BURIED WITH THE
 POLYAMIDE OR POLYETHYLENE PIPE TO FACILITATE LOCATING
 THE PIPE.
 A. ONE END OF THE TRACER WIRE SHALL BE BROUGHT ABOVE
 GROUND AT A BUILDING WALL OR RISER.
 B. THE TRACER WIRE OR TAPE SHALL NOT BE IN DIRECT
 CONTACT WITH THE POLYAMIDE OR POLYETHYLENE PIPE.
  
  
 END OF COMMENTS
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, AA TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715
  