| 2019-05-07 10:26:35 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. PROVIDE ACCURATE LOAD CALCULATION INCLUDING ALL |
| | LOADS AS PRESCRIBED IN THE FBC RESIDENTIAL. THIS SHOULD |
| | INCLUDE THE SQUARE FOOTAGE CALCULATION AND EACH |
| | ADDITIONAL LOAD SPECIFIED. THE MECHANICAL PLAN SHOWS 3 |
| | AC SYSTEMS, BUT ONLY TWO ARE INCLUDED ON ELECTRICAL |
| | PLAN. THE LOAD CALCULAITON SHOULD INCLUDE THE LARGER OF |
| | THE AC LOAD AT 100%, OR 65% OF THE HEAT LOAD, WHICHEVER |
| | IS GREATER. NEC 220; FBC RE E3602.2 |
| | 2. PROVIDE COMPLIANCE: A MINIMUM OF 75 PERCENT OF THE |
| | LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL |
| | BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF |
| | THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL |
| | CONTAIN ONLY HIGH EFFICACY LAMPS. A NOTE WILL SUFFICE. |
| | FBC EC C405.1, R404.1 |
| | 3. PROVIDE SMOKE/CO ALARMS IN EACH LOCATION REQUIRED |
| | PER CODE, INCLUDING EACH LEVER OF THE STRUCTURE. FBC RE |
| | R314.3, R315.1; WPB FBC 107.2.1 |
| | 4. A GFCI PROTECTED RECEPTACLE OUTLET ON A 20 AMP |
| | CIRCUIT IS REQUIRED WITHIN 3 FEET OF EACH BASIN. |
| | PROVIDE CORRECTION FOR POWDER BATH. NEC 210.11(C)(3), |
| | 210.52(D); FBC RE E3703.4, E3901.6 |
| | 5. DINING ROOM RECEPTACLE AND LIGHTING OUTLETS ARE |
| | SHOWN ON THE SAME CIRCUIT. PROVIDE CORRECTION. NEC |
| | 210.52(B)(2); FBC RE E3703.2 |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY |
| | REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED |
| | SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD |
| | SHEETS. |
| | |