| 2019-04-12 16:00:48 | 04/12/2019 1ST GAS REVIEW**DENIED** WITH COMMENTS | | | | | | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS | | | TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE | | | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. | | | | | | 1. THE ADDRESS OF THE PROJECT OR RESIDENCE MUST BE ON | | | PLAN. WPB AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION | | | ON CONSTRUCTION DOCUMENTS. | | | 2. SHOWS THE BTU LOAD OF 323 ON ISOMETRIC AND SPECS ON | | | THE KOHLER IS 281 BTU, PLEASE REFLECT THAT ON YOU | | | ISOMETRIC. THERE IS A TOTAL OF 522 BTU?S ON THE RISER | | | DIAGRAM WHERE IS THE OTHER 91 BTU GOING TO? 2017 FBC | | | FUEL GAS RES. SEC G2413.2 MAXIMUM GAS DEMAND. | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & | | | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS | | | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL | | | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE | | | REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO | | | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED | | | COOPERATION. | | | | | | LUIS A. CRESPO | | | PLUMBING INSPECTOR / | | | PLUMBING PLAN REVIEW | | | AVAILABLE FROM 1:00 PM TO 4:00 PM | | | [email protected] | | | 561-805-6720 | | | |
|