Plan Review Notes For Permit 19031348
Permit Number 19031348
Review Stop B
Sequence Number 1
Notes
Date Text
2019-04-29 14:45:172017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19031348
 ADD: 525 OKEECHOBEE BLVD. 8TH FLOOR RESTROOM RENOVATION
 CONT: HOLT LEE
 TEL: 954-725-4881
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. 04/29/2019
 ACTION: DENIED
  
 1) THE BUILDING REVIEWER HAS THE SAME ISSUE AS THE
 PLUMBING REVIEWER.
 1A) SHEET 005-A3.1 RESTROOM ELEVATIONS DOES NOT SHOW
 COMPLIANCE WITH THE HEIGHT OF THE GRAB BARS. 2017
 FBC-ACCESSIBILITY CODE SECTION 609.4 POSITION OF GRAB
 BARS. GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL
 POSITION, 33 INCHES MINIMUM AND 36 INCHES MAXIMUM ABOVE
 THE FINISH FLOOR MEASURED TO THE TOP OF THE GRIPPING
 SURFACE, NOT CENTERLINE.
  
 1B) SHEET 005-A3.1 RESTROOM ELEVATIONS DOES NOT SHOW
 COMPLIANCE WITH THE 2017 FBC-ACCESSIBILITY CODE SECTION
 604.5.1 THE SIDE WALL GRAB BAR SHALL BE 42 INCHES (1065
 MM) LONG MINIMUM, LOCATED 12 INCHES (305 MM) MAXIMUM
 FROM THE REAR WALL AND EXTENDING 54 INCHES (1370 MM)
 MINIMUM FROM THE REAR WALL.
  
 1C) SHEET 005-A3.1 RESTROOM ELEVATIONS DOES NOT SHOW
 COMPLIANCE WITH THE 2017 FBC-ACCESSIBILITY CODE SECTION
 604.5.2 REAR WALL. THE REAR WALL GRAB BAR SHALL BE 36
 INCHES (915 MM) LONG MINIMUM AND EXTEND FROM THE
 CENTERLINE OF THE WATER CLOSET 12 INCHES (305 MM)
 MINIMUM ON ONE SIDE AND 24 INCHES (610 MM) MINIMUM ON
 THE OTHER SIDE.
  
 2) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved