| 2019-04-04 15:07:05 | GAS 1ST REVIEW**DENIED** |
| | |
| | YOUR PLAN CALLS OUT A GAS POOL HEATER WAS REMOVED AND |
| | ELC ONE INSTALLED IN ITS PLACE WITH NO OTHER GAS |
| | APPLIANCE'S IN HOME. CITY RECORDS (PERMIT#07040709) |
| | SHOW EXISTING HWH, FIRE PLACE, AND FUTURE GRILL AND |
| | RANGE. |
| | |
| | |
| | 1) THE PLANS INDICATE AN EXISTING GAS METER. THE BTU |
| | LOAD OF THE EXISTING GAS SYSTEM MUST BE ADDED INTO THE |
| | TOTAL BTU LOAD ON THE SYSTEM TO ENSURE THE EXISTING |
| | SYSTEM IS PROPERLY SIZED. IF UNDERSIZED, THE EXISTING |
| | SYSTEM MUST BE REDONE TO ENSURE A SAFE OPERATING |
| | SYSTEM. SUBMIT A GAS PIPING RISER DIAGRAM THAT SHOWS |
| | THE TYPE OF EXISTING APPLIANCE, THE BTU LOAD OF EACH |
| | APPLIANCE, THE PIPE SIZE AND TYPE OF PIPE TO EACH |
| | APPLIANCE, AND THE DISTANCE OF THE LONGEST LENGTH OF |
| | PIPING FROM THE POINT OF DELIVERY TO THE MOST REMOTE |
| | OUTLET AND THE LOAD OF THE SECTION. NOTE: IF THE |
| | EXISTING SYSTEM IS LESS THAN A 2 PSI SYSTEM AND THE |
| | SYSTEM PRESSURE IS INCREASED TO 2 PSI, A LINE PRESSURE |
| | REGULATOR IS REQUIRED AT ALL THE EXISTING APPLIANCES. |
| | FGC SECS. 401.4, 401.8, 402.1, 402.2, 402.3 OR FBCR |
| | SECS.G2412.4, G2412.8, G2413.1, G2413.2, G2413.3. |
| | |
| | 2) YOU PLAN HAS L.P TANK SUBMITTAL INFORMATION BUT AN |
| | EXISTING TANK ALREADY EXIST. ARE YOU REPLACE THE |
| | EXISTING 500 L.P TANK? PLEASE CLARIFY. FBC 107.2.1 |
| | |
| | 3) LIST THE BTU LOAD OF EACH APPLIANCE AND THE TOTAL |
| | BTU LOAD ON THE SYSTEM INCLUDING FUTURE FIXTURES. REFER |
| | TO THE 2017 FBC-FUEL GAS SECS.401.8, 402.2, AND TABLES |
| | 402.4 (1) THRU 402.4 (37) OR 2017 FBC-RES. SEC. |
| | G2413.3, G2413.4 AND TABLES G2413.4 (1 ) THROUGH |
| | G2413.4 (21). |
| | |
| | TIM HUNT |
| | PLUMBING PLANS EXAMINER |
| | BUILDING DIVISION |
| | CITY OF WEST PALM BEACH |