| 2019-08-02 13:23:23 | 1) THERE ARE TWO GAS DRAWINGS IN THIS SUBMITTAL. ONE | | | SHOWS A 15 KW GENERATOR AND THE OTHER SHOWS A 22 KW | | | GENERATOR. WHAT ARE YOU INSTALLING? YOU SHOW RWO | | | DIFFERENT GENERATORS WITH THE SAME BTU LOAD OF 281,000 | | | WHICH DOES NOT THE MATCH THE BTU LOAD IN THE | | | MANUFACTURER'S INSTALLATION MANUAL. SUBMIT TWO COPIES | | | OF A GAS DRAWING THE CORRECT SIZE GENERATOR AND BTU | | | LOAD. WPB AMEND. TO FBC SEC. 107.2.1. | | | 2) A UNION IS REQD. WITHIN ONE FOOT UPSTREAM OR | | | DOWNSTREAM OF EACH REGULATOR. SHOW THIS ON THE PLAN. | | | |
|