| 2019-07-15 10:12:31 | ROOFING PROVISO UNDER BUILDING PERMIT: |
| | |
| | 1) THE ROOFING PRODUCT APPROVAL SUBMITTED (17-1227.05 |
| | CARLISLE SURE WELD SINGLE PLY TPO ROOF SYSTEMS OVER |
| | LIGHTWEIGHT CONCRETE DECKS) AND REVIEWED BY THE |
| | DESIGNER OF RECORD HAS NOT IDENTIFIED WHICH SUB-SYSTEM |
| | IS TO BE INSTALLED AND ASSOCIATED PRESSURES. |
| | |
| | 2) THE ROOFING PERMIT WILL REQUIRE A SEPARATE PLAN |
| | REVIEW FOR CODE COMPLIANCE. FOR ALL ROOFING PRODUCTS |
| | PLEASE IDENTIFY ALL ROOFING SUB-SYSTEMS AND THEIR |
| | ASSOCIATED PRESSURES FOR ROOF ZONE # 1. REVIEW THE |
| | PRODUCT APPROVAL LIMITATIONS, IF ENHANCED FASTENING IS |
| | ALLOWED FOR ROOF ZONES 2 & 3. FASTENER DENSITIES SHALL |
| | BE INCREASED FOR EITHER OR BOTH INSULATION & THE BASE |
| | SHEET AS CALCULATED IN COMPLIANCE WITH ROOFING |
| | APPLICATION STANDARDS RAS 117. CALCULATION PREPARED, |
| | SIGNED AND SEALED BY A FLORIDA REGISTERED PROFESSIONAL |
| | ENGINEER OR REGISTERED ARCHITECT. 1609.6.4.4.1 |
| | COMPONENTS & CLADDING. |
| | |
| | 3) SHEET S-100 SHOWS BOTH WELDED AND BOLTED |
| | CONNECTIONS. IF THERE ARE FIELD WELDED CONNECTIONS THEN |
| | SHOW COMPLIANCE FOR FIELD WELDED CONNECTIONS AND BOLTED |
| | CONNECTIONS. |
| | THE CONTRACTOR IS REQUIRED TO PROVIDE WELD PROCEDURE |
| | SPECIFICATIONS & WELDER OPERATOR PERFORMANCE |
| | QUALIFICATION RECORDS IN ACCORDANCE WITH THE REFERENCED |
| | STANDARDS AT TIME OF INSPECTION. IN ACCORDANCE WITH THE |
| | AMERICAN WELDING SOCIETY. |
| | 2017 FBC-B 2204.1 WELDING |
| | 2017 FBC-B 2204.2 BOLTING. |
| | |
| | JAMES A. WITMER BN, PX, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | |
| | |