2019-05-01 13:38:22PLUMBING 1ST REVISION REVIEW**DENIED**
  
 1) SHT. P1.2 CALLS OUT OF 2 NEW RPZ BACKFLOWS. PROVIDE
 NOTE THAT BACKFLOWS ARE REQUIRED TO HAVE A SEPERATE
 PERMIT AND ARE TO BE LEAD-FREE. , WPB CROSS CONNECTION
 MANUAL 2017
  
 2) PROVIDE DETAIL WHERE THE DISCHARGE PIPING FOR THE
 RELIEF VALVES OF THE BACKFLOW DEVICES IS DISCHARGING
 TO. FBC 107.2.1
  
 3) SHT. P2.1 NOTE #18 CALLS OUT TO INSTALL NEW 2" FLOOR
 SINK, NOTE #16 CALLS OUT NEW WASHING MACHINE BOX, SHT.
 A1.2 CALLS FOR NEW SINK NOTE #5 WHICH ON DEMO PLAN ON
 IN A DIFFERENT LOCATION. ALL THREE ARE NOT SHOWN ON
 PLUMBING ISOMETRIC ON SHT. P0.1.PLEASE ADVISE AND
 PROVIDE A COMPLETE SANITARY RISER DRAWING. FBC 107.3.5
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
  
  