| Plan Review Notes For Permit 19031293 |
| Permit Number |
19031293 |
|
| Review Stop |
MEDGAS |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2019-05-01 13:39:54 | PLUMBING 1ST REVISION REVIEW**DENIED** | | | | | | 1) PLAN'S THAT CONTAIN MED GAS PIPING IS SO CONGRESSED | | | THAT IT IS IMPOSSIBLE TO PERFORM AN ACTUATE PLAN | | | REVIEW. PROVIDE FLAT DRAWINGS OF ALL MED GAS PIPING IN | | | SMALLER SECTION ON FULL SHEETS AND PROVIDE A COMPLETE | | | ISOMETRIC DRAWING TO INCLUDE DETAIL PIPING OF ALL NEW | | | MED GAS EQUIPMENT. FBC 107.3.5. | | | | | | 2) PROVIDE COMPLETED INSTALLATION MANUALS FOR ALL NEW | | | MED GAS EQUIPMENT. FBC 107.3.5 | | | | | | 3) CERTIFICATION FOR THE PLUMBING CONTRACTOR AND ANY | | | AND ALL EMPLOYEES SHOWING MED GAS CERTIFIED IS REQUIRED | | | TO BE SUBMITTED PRIOR TO THE MED GAS PERMIT BEING | | | ISSUED. FBC 105.1 | | | | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | | THE PREVIOUSLY REVIEWED SHEETS. | | | | | | | | | | | | PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR | | | BUILDING DIVISION | | | CITY OF WEST PALM BEACH | | | 401 CLEMATIS STREET, 1ST FLOOR | | | WEST PALM BEACH, FL 33401 | | | 561-248-2703 | | | [email protected] | | | [email protected] | | | |
|