| 2019-05-07 12:37:55 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | ASHRAE 170-2008 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) PROVIDE AC COOLING AND HEATING CALCULATIONS FOR THE |
| | NEW AHU'S AND FAN COIL SYSTEMS IN ACCORDANCE WITH |
| | SECTION C403.2.1 FBC EC. |
| | |
| | 2) COMMISSIONING OF THE MECHANICAL AND SERVICE WATER |
| | HEATING SYSTEMS IS REQUIRED PER SECTION C408.2 FBC-17 |
| | ENERGY CONSERVATION. SUBMIT A COMMISSIONING PLAN AS |
| | OUTLINED IN SECTION C408.2.1 AND DESCRIBED IN SECTIONS |
| | C403.2.2- C408.2.3.3. PLEASE NOTE THAT A COPY OF THE |
| | COMMISSIONING REPORT SHALL BE SUBMITTED FOR REVIEW AT |
| | FINAL INSPECTION. |
| | |
| | 3) SHEET M7.3: THE AHU-2 SUMMARY IS MISSING THE MINIMUM |
| | REQUIRED 2 OA ACH. THE AHU-3 SUMMARY IS MISSING THE |
| | MINIMUM REQUIRED 8 TOTAL ACH- TABLE 7-1 ASHRAE |
| | 170-2008. |
| | |
| | 4) M2.2, 3.2, 4.2, & 5.2: THE LOW SIDE WALL RETURN |
| | GRILLS IN THE OR'S SHALL BE INSTALLED APRROXIMATELY 8 |
| | IN. ABOVE THE FLOOR- SECTION 7.4.1 ASHRAE 170-2008. |
| | |
| | 5) M8.2: PLEASE INDICATE THE PRESSURE DIFFERENTIAL |
| | VALUE TO BE MAINTAINED BETWEEN THE OR'S AND ALL |
| | ADJOINING ROOMS AND SPACES- SECTION 7.4.1 ASHRAE |
| | 170-2008. REFER TO NOTE 1.3 (3) ON THE PLAN. |
| | |
| | 6) THE WIND LOAD ENGINEERING FOR THE RTU'S AND THE |
| | EXHAUST FANS ON THE ROOF IS INCOMPLETE. REFER TIO THE |
| | BUILDING REVIEW COMMENTS AND COMPLY- SECTION 301.15 FBC |
| | M. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS |
| | |