| Plan Review Notes For Permit 19031262 |
| Permit Number |
19031262 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2019-03-28 18:32:37 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC SIXTH EDITION (2017) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | REVISION IS DENIED | | | | | | 1) THE BUILDING IS LOCATED IN EXPOSURE C WITH A 170 MPH | | | VULT WINDSPEED. THE MAXIMUM DESIGN PRESSURE FOR THE | | | SYSTEM YOU SELECTED IS -60 PSF. THIS IS NOT ADEQUATE AT | | | THE CORNER AND PERIMETER AREAS. GENERAL LIMITATION | | | NUMBER 7 ON THE NOA, ALLOWS FOR ENHANCED FASTENING IN | | | THESE AREAS TO INCREASE UPLIFT PRESSURES. SUBMIT SIGNED | | | AND SEALED RAS 117 CALCULATIONS. |
|