| 2019-03-29 11:50:36 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | 1) THERE IS INSUFFICIENT INFORMATION ON THE PLAN SHEETS |
| | AS TO WHAT IS BEING DONE. |
| | |
| | PLEASE PROVIDE DETAILS AS TO WHAT WORK IS BEING DONE AT |
| | EACH APARTMENT. |
| | |
| | |
| | |
| | 2) THERE IS ONLY ONE PLAN SHEET. |
| | |
| | ARE ALL THE UNITS THE SAME? |
| | |
| | IF THERE ARE ANY DIFFERENCES, EACH FLOOR LAYOUT SHALL |
| | BE INCLUDED ON A SEPARATE SHEET. |
| | |
| | |
| | |
| | 3) PLEASE PROVIDE A SITE PLAN SHOWING THE LOCATION OF |
| | EACH UNIT. |
| | |
| | |
| | |
| | |
| | 4) THERE ARE NO INDICATIONS OF SMOKE ALARMS. SMOKE |
| | ALARMS ARE REQUIRED PER THE LIFE SAFETY CODE FOR |
| | EXISTING APARTMENTS. |
| | |
| | PER NFPA 101 |
| | |
| | 31.3.4.5 SMOKE ALARMS. |
| | 31.3.4.5.1* IN BUILDINGS OTHER THAN THOSE EQUIPPED |
| | THROUGHOUT WITH AN |
| | EXISTING, COMPLETE AUTOMATIC SMOKE DETECTION SYSTEM, |
| | SMOKE ALARMS |
| | SHALL BE INSTALLED IN ACCORDANCE WITH 9.6.2.10, AS |
| | MODIFIED BY 31.3.4.5.2, |
| | OUTSIDE EVERY SLEEPING AREA IN THE IMMEDIATE VICINITY |
| | OF THE BEDROOMS |
| | AND ON ALL LEVELS OF THE DWELLING UNIT, INCLUDING |
| | BASEMENTS. |
| | 31.3.4.5.2 SMOKE ALARMS REQUIRED BY 31.3.4.5.1 SHALL |
| | NOT BE REQUIRED TO |
| | BE PROVIDED WITH A SECONDARY (STANDBY) POWER SOURCE. |
| | 31.3.4.5.3 IN BUILDINGS OTHER THAN THOSE EQUIPPED |
| | THROUGHOUT WITH AN |
| | EXISTING, COMPLETE AUTOMATIC SMOKE DETECTION SYSTEM OR |
| | A COMPLETE, |
| | SUPERVISED AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE |
| | WITH 31.3.5, |
| | SMOKE ALARMS SHALL BE INSTALLED IN EVERY SLEEPING AREA |
| | IN |
| | ACCORDANCE WITH 9.6.2.10, AS MODIFIED BY 31.3.4.5.4. |
| | 31.3.4.5.4 SMOKE ALARMS REQUIRED BY 31.3.4.5.3 SHALL BE |
| | PERMITTED TO BE |
| | BATTERY POWERED. |
| | |
| | PLEASE INDICATE ON EACH PLAN SHEET THE LOCATION THE SA |
| | AND HOW THEY WILL BE POWERED. |
| | |
| | |
| | |
| | 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |