Plan Review Notes
Plan Review Notes For Permit 19031242
Permit Number 19031242
Review Stop E
Sequence Number 2
Notes
Date Text
2019-05-13 07:19:03ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. AS PER LAST PLAN REVIEW COMMENTS PROVIDE LOAD CALC
 FOR PANEL "A" INCLUDING ALL LOADS BOTH EXISTING AND
 NEW. "LOAD CALC" PROVIDED ON SHEET E.1 IS NOT A LOAD
 CALC. THAT MERELY SHOWS THE NEW PROPOSED LOAD. THERE
 ARE SEVERAL BREAKERS ALREADY IN PANEL A:
  
 1-40AMP LABELED "S BTS"
  
 1-40AMP LABELED "UMTS"
  
 1-100AMP LABELED "IV BTS"
  
 1-40AMP LABELED "EXISTING SSC"
  
 NEC 220, FBC 107.2.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
  