| Plan Review Notes For Permit 19031242 |
| Permit Number |
19031242 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2019-05-13 07:19:03 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | 1. AS PER LAST PLAN REVIEW COMMENTS PROVIDE LOAD CALC | | | FOR PANEL "A" INCLUDING ALL LOADS BOTH EXISTING AND | | | NEW. "LOAD CALC" PROVIDED ON SHEET E.1 IS NOT A LOAD | | | CALC. THAT MERELY SHOWS THE NEW PROPOSED LOAD. THERE | | | ARE SEVERAL BREAKERS ALREADY IN PANEL A: | | | | | | 1-40AMP LABELED "S BTS" | | | | | | 1-40AMP LABELED "UMTS" | | | | | | 1-100AMP LABELED "IV BTS" | | | | | | 1-40AMP LABELED "EXISTING SSC" | | | | | | NEC 220, FBC 107.2.1 | | | | | | END OF COMMENTS. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | | PREVIOUSLY REVIEWED SHEETS. | | | CODES IN EFFECT: | | | | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE 2017 6TH ED. | | | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017 | | | 6TH EDITION | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | V/R, | | | | | | FRANK GIAQUINTO III | | | ELECTRICAL INSPECTOR | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | [email protected] | | | |
|