| 2019-08-30 08:48:59 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | FAC = FLORIDA ADMINISTRATIVE CODE |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. PROVIDE EXTERIOR LIGHTING CONTROLS AS SPECIFIED IN |
| | THE FBC ENERGY CONSERVATION. FBC EC C405.2.5 |
| | 2. PLAN SHEETS INCLUDE FIVE DIFFERENT GATEWAY PLANS. |
| | THIS PERMIT APPLICATION IS FOR GATEWAY D. REMOVE ALL |
| | SHEETS NOT PERTINENT TO THIS APPLICAITON. WPB FBC |
| | 107.2.1 |
| | 3. RISER DIAGRAM DOES NOT INDICATE WHERE THE FEED IS |
| | FROM. PROVIDE DETAILS OF ELECTRICAL SOURCE. WPB FBC |
| | 107.2.1; NEC 215.5 |
| | 4. LOAD CALCULATION AND PANEL SCHEDULE NOT PROVIDED AS |
| | PREVIOUSLY REQUESTED. PROVIDE ACCURATE LOAD CALCULATION |
| | FOR SERVICE, INCLUDE EXISTING AND NEW LOADS TO CONFIRM |
| | CAPACITY OF SERVICE IS ADEQUATE. PROVIDE PANEL SCHEDULE |
| | INDICATING ANY NEW OR ALTERED CIRCUITS, THE WIRE AND |
| | BREAKER SIZE FOR THESE CIRCUITS, AND AFCI OR GFCI |
| | PROTECTION WHERE APPLICABLE TO COMPLY WITH CODE. NEC |
| | 210.8, 210.12, 210.19, 210.20, 215.5, 220, 408.4; WPB |
| | FBC 107.2.1 |
| | 5. WHAT IS THE DISTANCE FROM THE FEED TO THE SIGN? |
| | PROVIDE VOLTAGE DROP CALCULATIONS TO COMPLY WITH CODE. |
| | FBC EC C405.6.3 |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY |
| | REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED |
| | SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD |
| | SHEETS. |
| | |