| 2019-06-04 06:36:03 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. NOTE ON MONUMENT SIGN PLAN QUOTING "600.6A1 EX #2" |
| | THERE IS NO EXCEPTION #2 TO 600.6A1 AND EXCEPTION #1 |
| | DOESN'T APPLY TO THIS APPLICATION. |
| | |
| | 2. DISCONNECT FOR MONUMENT SIGN SHOWN ON PLAN DOES NOT |
| | MEET THE REQUIREMENTS OF 600.6A1. DISCONNECT MUST |
| | DISCONNECT ALL BRANCH CIRCUITS CONDUCTORS AT THE POINT |
| | THEY ENTER THE SIGN. WHEN DISCONNECT IS OPEN ALL 120V |
| | CONDUCTORS IN SIGN MUST BE DISCONNECTED. PLEASE COMPLY. |
| | NEC 600.6A1 |
| | |
| | 3. DISCONNECT ON SHEET #3 OF PLAN DOES NOT COMPLY WITH |
| | 600.6A1. PLEASE PROVIDE CORRECTION. |
| | |
| | 4. DISCONNECT ON SHEET #15 OF PLAN DOES NOT COMPLY WITH |
| | 600.6A1. PLEASE PROVIDE CORRECTION. |
| | |
| | 5. DISCONNECT ON SHEET # 17 OF PLAN DOES NOT COMPLY |
| | WITH 600.6A1. PLEASE PROVIDE CORRECTION. |
| | |
| | |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | CODES IN EFFECT: |
| | |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE 2017 6TH ED. |
| | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| | 6TH EDITION |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | V/R, |
| | |
| | FRANK GIAQUINTO III |
| | ELECTRICAL INSPECTOR |
| | ELECTRICAL PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | [email protected] |
| | CELL: 561-657-1653 |
| | |