| 2019-04-19 06:39:12 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. EXTERNAL 120V DISCONNECT REQUIRED FOR ALL SIGNS |
| | (WALL AND MONUMENT) MUST CONFORM WITH THE REQUIREMENTS |
| | OF 600.6A1 NEC. DISCONNECT MUST BE WITHIN SIGHT OF SIGN |
| | AND SHUT DOWN BRANCH CIRCUIT CONDUCTORS FEEDING SIGN. |
| | PROVIDE CORRECTIONS |
| | |
| | 2. PROVIDE NOTE ON PLAN FOR STATING ALL EXTERNAL SIGNS |
| | WILL BE CONTROLLED BY AN ASTRONOMICAL TIME CLOCK/W |
| | BATTERY BACKUP OR BUILDING MANAGMENT SYSTEM TO CONFORM |
| | WITH ENERGY CONSERVATION EXTERNAL LIGHTING REQUIREMENTS |
| | OF FBC EC 405.2.4 |
| | |
| | 3. NO WIRING DIAGRAM PROVIDED FOR MONUMENT SIGN. |
| | PROVIDE ELECTRICAL PLAN FOR MONUMENT SIGN. SHOW |
| | EXTERNAL DISCONNECT REQUIRED BY 600.6A1 AS DESCRIBED IN |
| | PLAN REVIEW COMMENT #1. |
| | |
| | 4. NO WIRING DIAGRAM PROVIDED FOR "ATM" SIGNS. PROVIDE |
| | ELECTRICAL PLAN FOR "ATM" SIGNS. SHOW EXTERNAL |
| | DISCONNECT REQUIRED BY 600.6A1 AS DESCRIBED IN PLAN |
| | REVIEW COMMENT #1. |
| | |
| | 5. VALUE SEEMS LOW FOR AMOUNT OF WORK SHOWN. PROVIDE |
| | CONTRACT INCLUDING ALL MATIERALS AND LABOR. SIGNED BY |
| | BOTH CONTRACTOR AND OWNER. |
| | |
| | FBC 109.3 BUILDING PERMIT VALUATION. FOR PERMITTING |
| | PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE |
| | TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL, |
| | ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH, |
| | RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES, |
| | MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY |
| | LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST |
| | PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS |
| | SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY |
| | INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT |
| | VALUATION SHALL BE SET BY THE BUILDING OFFICIAL. |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | CODES IN EFFECT: |
| | |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE 2017 6TH ED. |
| | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| | 6TH EDITION |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |