| Plan Review Notes For Permit 19031199 |
| Permit Number |
19031199 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2019-03-29 08:49:11 | FLORIDA BUILDING CODE 2014 5TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH ED | | | NFPA 70 2011 EDITION | | | | | | JAKE LEAHY | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | PG. E-2 OUTSIDE BEDROOM #3 MISSING SMOKE ALARM/CO | | | DETECTOR | | | | | | PG. E-3 RISER AND PANEL SCHEDULES DON'T MATCH | | | PANEL "A" DOES NOT FEED PANEL "C" | | | METER MAIN PANEL SCHEDULE NOT SHOWN 2-P 80A FEEDS ? | | | LOAD CALCULATION SHOWS LOADS OF 7KW FOR PANEL "C" AND | | | 10KW FOR PANEL "P" AND THEN DEMANDED AGAIN ON LOAD | | | CALC? | | | YOU CAN NOT DEMAND LOADS FROM "C" AND "P" TWICE. SHOW | | | HOW LOADS ARE CALCULATED TO GET 7K AND 10K | | | SHOWS A REFERENCE TO A GENERATOR ON PAGE "GENERATOR IS | | | NOT SHOWN" PLEASE INCLUDE IN RISER DIAGRAM. |
|