| 2019-04-10 10:09:43 | 1ST REVIEW: |
| | 2017 FLORIDA BUILDING CODE 6TH EDITION |
| | 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH |
| | EDITION |
| | 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH |
| | EDITION |
| | 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH |
| | EDITION |
| | |
| | GAS COMMENTS: |
| | |
| | 1. PROVIDE DETAIL OF HOW THE END OF THE PIPING WILL BE |
| | SECURED SO THAT GAS WILL NOT BE RELEASED INTO SPACE IF |
| | SOME ONE ENERGIZES THE 2" LINE A LOCKING VALVE AND CAP |
| | IS REQUIRED. PER WPB AMEND TO FBC 107.2.1 AND FBC FG |
| | 404.15 |
| | 2. PLACE NOTE ON PLAN . CITY OF WEST PALM BEACH PIPING |
| | AFFIDAVIT OR MANOMETER TEST DOCUMENT REQUIRED AT |
| | JOBSITE FOR FINAL INSPECTION. PER WPB AMEND TO FBC |
| | 107.2.1 |
| | 3. PLACE NOTE ON THE PLAN THAT PIPING IS FOR FUTURE USE |
| | NO APPLIANCES TO BE CONNECTED WITH OUT SEPARATE |
| | PERMIT.. PER WPB AMEND TO FBC 107.2.1 |
| | |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |