| 2019-06-11 15:20:55 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL |
| | MANUAL REVISED 2017 |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION |
| | FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH |
| | EDITION |
| | FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION |
| | FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION |
| | NFPA 30A |
| | FAC= FLORIDA ADMINISTRATIVE CODE |
| | FS = FLORIDA STATUTES |
| | |
| | |
| | 2ND REVIEW |
| | PLUMBING COMMEMTS: DENIED |
| | |
| | REGARDING THE RESPONSE LETTER (REF: PERMIT |
| | 17020652-RESPONSE LETTER), PLUMBING COMMENT RESPONSE |
| | THAT THE REVISED PLUMBING RISER IS ON SHEET E-1 IS NOT |
| | ACCURATE. THERE IS NO REVISED PLUMBING RISER ON E-2. IF |
| | THERE IS TO BE A REVISED RISER DIAGRAM ON E-2, THEN THE |
| | DIAGRAM ON S-2 SHALL BE REMOVED. |
| | AS THERE IS NO REVISED DRAWING IT APPEARS NO ACTION HAS |
| | BEEN TAKEN IN RESPONSE TO THE COMMENTS MADE IN THE |
| | FIRST REVIEW. PLEASE SEE BELOW. |
| | |
| | 1. SHT. S-1 AND S-2 THE SEAL AND SIGNATURE OF THE |
| | ENGINEER APPEARS TO BE PHOTO COPIED THEY SHALL BE |
| | ORIGINAL. FAC 61G15-23.003 |
| | 2. REMOVE STAMP AND SIGNATURE OF PREVIOUS PLUMBING |
| | EXAMINER SHT. S-2 PER WPB AMEND TO FBC 107.2.1 |
| | 3. SHT S-2 THE PLUMBING SANITARY RISER IN THE BATHROOM |
| | GROUP ONLY ONE FIXTURE UP STREAM OF THE WET VENT IS |
| | ALLOWED THE LAVATORY SHALL CONNECT BETWEEN THE TOILET |
| | AND TUB. PER FBC RES P3108.2.1 |
| | |
| | END OF COMMENTS. |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS.ALL PLANS TO BE SIGNED |
| | AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS. |
| | |
| | |
| | |
| | JERALD SMITH |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | EMAIL [email protected] |
| | PHONE 561-805-6715 |
| | |
| | 19031173 3212 GREENWOOD AVE |