| Plan Review Notes For Permit 19031173 |
| Permit Number |
19031173 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2019-04-12 14:41:21 | 1ST REVIEW: | | | 2017 FLORIDA BUILDING CODE 6TH EDITION | | | 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION | | | 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH | | | EDITION | | | 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION | | | 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION | | | 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH | | | EDITION | | | 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH | | | EDITION | | | | | | PLUMBING COMMENTS: | | | | | | 1. SHT. S-1 AND S-2 THE SEAL AND SIGNATURE OF THE | | | ENGINEER APPEARS TO BE PHOTO COPIED THEY SHALL BE | | | ORIGINAL. FAC 61G15-23.003 | | | | | | 2. REMOVE STAMP AND SIGNATURE OF PREVIOUS PLUMBING | | | EXAMINER SHT. S-2 PER WPB AMEND TO FBC 107.2.1 | | | | | | 3. SHT S-2 THE PLUMBING SANITARY RISER IN THE BATHROOM | | | GROUP ONLY ONE FIXTURE UP STREAM OF THE WET VENT IS | | | ALLOWED THE LAVATORY SHALL CONNECT BETWEEN THE TOILET | | | AND TUB. PER FBC RES P3108.2.1 | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | | THE PREVIOUSLY REVIEWED SHEETS. | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561-805-6711 | | | [email protected] | | | |
|