2019-08-22 18:27:32THIRD BUILDING REVIEW COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 NOTE;
 THE COMMENTS REGARDING THE METAL STRUCTURE WERE NOT
 ADDRESSED AT ALL. PLEASE SEE BELOW FOR COPY OF
 COMMENTS. IF THERE IS ANY QUESTION, PLEASE FEEL FREE TO
 CONTACT ME.
  
 ORIGINAL COMMENT:
 1- DESIGN CRITERIA FOR METAL STRUCTURE PLANS SUBMITTED:
 A)ENGINEER STATES RISK CATEGORY III. ENGINEER NEEDS TO
 REVISE THE ULTIMATE AND NOMINAL DESIGN WIND SPEED AS
 REQUIRED BY SEC. 1609.3 FBC-BUILDING FOR RISK CATEGORY
 III.
 NOTE: THE CITY ULTIMATE DESIGN FOR RISK CATEGORY III
 AND IV IS 180 MPH. SEE SEC. 120.1 CITY AMENDMENTS.
  
 B) GENERAL NOTE #2 STATES THAT THIS IS A BUILDING FOR
 RISK CATEGORY I. COORDINATE WITH RISK CATEGORY
 SPECIFIED ON THE DESIGN CRITERIA. COORDINATE WITH ITEM
 ABOVE. SEC. 107.2.1 CITY AMENDMENTS.
  
 C) ENGINEER STATES WIND EXPOSURE "C". THE DESIGN
 PRESSURES SHOWN SEEM TO BE TO LOW FOR BUILDING EXPOSURE
 C. ENGINEER TO PROVIDE CALCULATIONS SHOWING HOW THE
 DESIGN PRESSURES WERE CALCULATED. NOTE: COORDINATE WITH
 ITEM #2(A) ABOVE. SEC. 107.2.1.2 CITY AMENDMENTS.
  
 D) ENGINEER TO SPECIFY IF THE DESIGN PRESSURES SHOWN
 ARE ULTIMATE DESIGN WIND SPEED OR NOMINAL DESIGN WIND
 SPEEDS. THE ULTIMATE WIND DESIGN WIND SPED NEEDS TO BE
 CONVERTED TO NOMINAL DESIGN WIND SPEEDS. SEC. 1609.3.1
 FBC-BUILDING.
  
 E) ENGINEER OF RECORD TO CLEARLY MARK ON THE PRODUCT
 APPROVAL SUBMITTED THE FASTENING OF THE METAL ROOF
 PANELS. NOTE: SEE TABLE "A" OF PRODUCT APPROVAL FOR
 MAXIMUM DESIGN PRESSURES AND COORDINATE WITH ITEMS
 #2(A) AND 2(C) ABOVE.
 SEC. 1609.1 FBC-BUILDING.
  
 F) ENGINEER OF RECORD TO CLEARLY MARK ON THE PRODUCT
 APPROVAL SUBMITTED THE FASTENING OF THE METAL WALL
 PANELS. NOTE: SEE TABLE "A" OF PRODUCT APPROVAL FOR
 MAXIMUM DESIGN PRESSURES AND COORDINATE WITH ITEMS
 #2(A) AND 2(C) ABOVE.
 SEC. 1609.1 FBC-BUILDING.
  
 2- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.001 FOR:
 A)METAL ROOF PANELS SPECIFIED ON PLANS.
  
 B)METAL WALL PANELS SPECIFIED ON PLANS.
  
 C) ROLL UP DOORS THAT MET THE DESIGN PRESSURES
 CALCULATED BY THE ENGINEER OF RECORD. COORDINATE WITH
 ITEM #2(A) AND #2(C) ABOVE.
 NOTE: DESIGN PRESSURES FOR ROLL UP DOOR MODEL 203
 SPECIFIED BY THE ENGINEER OF RECORD ON THE APPROVED
 PRODUCT LIST DOESN'T MEET THE DESIGN PRESSURES.
  
  
 IN ORDER TO AVOID MULTIPLE SUBMITTALS, PLEASE FEEL FREE
 TO CONTACT ME IF YOU HAVE ANY QUESTIONS REGARDING THESE
 COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  