2019-06-20 17:02:40SECOND BUILDING REVIEW COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 ORIGINAL COMMENT:
 1- SCOPE OF WORK IS NOT CLEAR. PERMIT APPLICATION
 SPECIFIES "INSTALLATION OF NEW BOOSTER PUMP CONNECTING
 TO EXISTING BIOSOIDS PROJECT". PLANS SUBMITTED ARE ONLY
 ELECTRICAL PLANS. THEY DON'T SHOW WHAT IS NEW A WHAT IS
 NOT. WHERE IS THE NEW PUMP GOING TO BE INSTALLED.
 OUTSIDE? INSIDE?. ARE THERE ANY SPECIFICATIONS REQUIRED
 FOR ANCHORING THE NEW PUMP FOR WIND LOADS?. PROVIDE
 FLOOR PLANS SHOWING THE COMPLETE SCOPE OF WORK. SEC.
 107.2.1 CITY AMENDMENTS.
  
 RESPONSE:
 SCOPE OF WORK STILL IS NO CLEAR. PLANS SUBMITTED SHOW
 ON SHEET C-YPP-02 THE CONSTRUCTION OF A CONCRETE SLAB
 FOR TEMPORARY PSW PUMPS. THIS IS OK. BUT IT IS NOT
 CLEAR WHY SUBMITTING SEPARATE ENGINEERED DRAWINGS FOR
 FOR A METAL STRUCTURE. THERE ARE NO PLANS SHOWING WHERE
 THIS STRUCTURE IS GOING TO BE INSTALLED. SEC. 107.2.1
 CITY AMENDMENTS.
  
 NEW COMMENTS:
 2- DESIGN CRITERIA FOR METAL STRUCTURE PLANS SUBMITTED:
 A)ENGINEER STATES RISK CATEGORY III. ENGINEER NEEDS TO
 REVISE THE ULTIMATE AND NOMINAL DESIGN WIND SPEED AS
 REQUIRED BY SEC. 1609.3 FBC-BUILDING FOR RISK CATEGORY
 III.
 NOTE: THE CITY ULTIMATE DESIGN FOR RISK CATEGORY III
 AND IV IS 180 MPH. SEE SEC. 120.1 CITY AMENDMENTS.
  
 B) GENERAL NOTE #2 STATES THAT THIS IS A BUILDING FOR
 RISK CATEGORY I. COORDINATE WITH RISK CATEGORY
 SPECIFIED ON THE DESIGN CRITERIA. COORDINATE WITH ITEM
 ABOVE. SEC. 107.2.1 CITY AMENDMENTS.
  
 C) ENGINEER STATES WIND EXPOSURE "C". THE DESIGN
 PRESSURES SHOWN SEEM TO BE TO LOW FOR BUILDING EXPOSURE
 C. ENGINEER TO PROVIDE CALCULATIONS SHOWING HOW THE
 DESIGN PRESSURES WERE CALCULATED. NOTE: COORDINATE WITH
 ITEM #2(A) ABOVE. SEC. 107.2.1.2 CITY AMENDMENTS.
  
 D) ENGINEER TO SPECIFY IF THE DESIGN PRESSURES SHOWN
 ARE ULTIMATE DESIGN WIND SPEED OR NOMINAL DESIGN WIND
 SPEEDS. THE ULTIMATE WIND DESIGN WIND SPED NEEDS TO BE
 CONVERTED TO NOMINAL DESIGN WIND SPEEDS. SEC. 1609.3.1
 FBC-BUILDING.
  
 E) ENGINEER OF RECORD TO CLEARLY MARK ON THE PRODUCT
 APPROVAL SUBMITTED THE FASTENING OF THE METAL ROOF
 PANELS. NOTE: SEE TABLE "A" OF PRODUCT APPROVAL FOR
 MAXIMUM DESIGN PRESSURES AND COORDINATE WITH ITEMS
 #2(A) AND 2(C) ABOVE.
 SEC. 1609.1 FBC-BUILDING.
  
 F) ENGINEER OF RECORD TO CLEARLY MARK ON THE PRODUCT
 APPROVAL SUBMITTED THE FASTENING OF THE METAL WALL
 PANELS. NOTE: SEE TABLE "A" OF PRODUCT APPROVAL FOR
 MAXIMUM DESIGN PRESSURES AND COORDINATE WITH ITEMS
 #2(A) AND 2(C) ABOVE.
 SEC. 1609.1 FBC-BUILDING.
  
 3- ENGINEER OF RECORD FOR THE PROJECT TO INDICATE ON
 PLANS THE LOCATION OF THE METAL STRUCTURE. IF HE IS NOT
 DESIGNING THE METAL STRUCTURE, THEN INDICATE ON PLANS
 THAT IS A DEFERRED SUBMITTAL. DESIGNER OF RECORD TO
 REVIEW AND APPROVE IN WRITING THE METAL STRUCTURE
 SUBMITTAL PRIOR TO SUBMITAL TO THIS OFFICE AS REQUIRED
 BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 4- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.001 FOR:
 A)METAL ROOF PANELS SPECIFIED ON PLANS.
  
 B)METAL WALL PANELS SPECIFIED ON PLANS.
  
 C) ROLL UP DOORS THAT MET THE DESIGN PRESSURES
 CALCULATED BY THE ENGINEER OF RECORD. COORDINATE WITH
 ITEM #2(A) AND #2(C) ABOVE.
 NOTE: DESIGN PRESSURES FOR ROLL UP DOOR MODEL 203
 SPECIFIED BY THE ENGINEER OF RECORD ON THE APPROVED
 PRODUCT LIST DOESN'T MEET THE DESIGN PRESSURES.
  
  
 5- WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 PLEASE, INSERT CORRECTED PAGES INTO THE SUBMITTAL AND
 REMOVE/VOID THE PREVIOUSLY REVIEWED SHEETS.
  
 PLEASE DON'T STAPLE OLD DRAWINGS/DOCUMENTS . SUBMIT OLD
 DRAWINGS/DOCUMENTS FOR REFERENCE.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  