Plan Review Notes
Plan Review Notes For Permit 19031168
Permit Number 19031168
Review Stop ENG
Sequence Number 1
Notes
Date Text
2019-07-03 10:28:50FAILED:
  
 1. AS OF DECEMBER 20, 2015 THE CITY OF WEST PALM BEACH
 CROSS-CONNECTION CONTROL MANUAL HAS BEEN REVISED,
 MAKING KNOWN THAT "ALL BACKFLOW DEVICES MUST BE LEAD
 FREE."
 FOR MORE INFORMATION REFER TO THE LINK BELOW:
 HTTP://WPB.ORG/DEPARTMENTS/PUBLIC-UTILITIES/FORMS-PUBLI
 CATIONS/BACKFLOW-CROSS-CONNECTION-CONTROL-MANUAL
  
 2. FO THIS APPLICATION CALL OUT BACFLOW TO BE A RPPA
 (REDUCED PRESSURE PRICIPLE ASSEMBLY). SUBMIT
 SPECIFICATION SHEET
 WITH REVISIONS TO PLAN M-ADF-40. DEVICE MUST BE "USC
 APPROVED" AND "LEAD FREE".
  
 FEEL FREE TO E-MAIL ME SHOULD YOU REQUIRE OUR REVIEW OF
 THE DEVICE PRIOR TO RESUBMISSION.
  