| 2019-04-18 15:45:13 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. NO ADDRESS ON PLANS, PROVIDE DETAILS. ALSO, CLEARLY |
| | SHOW WHAT IS NEW WORK ON PLAN. CURRENT DRAWING IS |
| | DIFFICULT TO ASCERTAIN WHAT IS NEW OR EXISTING. WPB FBC |
| | 107.2.1 |
| | 2. SHEET E-04 SHOW A PANEL SCHEDULE FOR PANEL |
| | "LP-TEMP". WHERE IS THIS PANEL FED FROM? SAME SHEET |
| | ALSO SHOW CIRCUITS FOR PUMP ROOM COMING FROM PANEL |
| | "LP-PSW". PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR |
| | ALTERED CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE |
| | CIRCUITS, AND GFCI PROTECTION WHERE APPLICABLE TO |
| | COMPLY WITH CODE. NEC 210.8, 210.19, 210.20, 215.5, |
| | 408.4 |
| | 3. SHEET E-04 SHOWS WIRING GOING TO 4 PUMP MOTORS, BUT |
| | THERE IS NO INDICATION OF WIRE SIZE, CIRCUIT SIZE, OR |
| | LOAD. PROVIDE DETAILS TO CONFIRM CODE COMPLIANCE. NEC |
| | 210.19, 210.20, 215.5, 408.4; WPB FBC 107.2.1 |
| | 4. PROVIDE MANUFACTURER SPEC SHEET FOR PUMP CONTROLLER. |
| | NEC 110.3; WPB FBC 107.2.1 |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY |
| | REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED |
| | SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD |
| | SHEETS. |
| | |