Plan Review Notes
Plan Review Notes For Permit 19031168
Permit Number 19031168
Review Stop B
Sequence Number 1
Notes
Date Text
2019-05-02 12:01:07BUILDING REVIEW COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 NOTE: ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
 SEC. 801.3 FBC-EXISTING BUILDING.
  
 1- SCOPE OF WORK IS NOT CLEAR. PERMIT APPLICATION
 SPECIFIES "INSTALLATION OF NEW BOOSTER PUMP CONNECTING
 TO EXISTING BIOSOIDS PROJECT". PLANS SUBMITTED ARE ONLY
 ELECTRICAL PLANS. THEY DON'T SHOW WHAT IS NEW A WHAT IS
 NOT. WHERE IS THE NEW PUMP GOING TO BE INSTALLED.
 OUTSIDE? INSIDE?. ARE THERE ANY SPECIFICATIONS REQUIRED
 FOR ANCHORING THE NEW PUMP FOR WIND LOADS?. PROVIDE
 FLOOR PLANS SHOWING THE COMPLETE SCOPE OF WORK. SEC.
 107.2.1 CITY AMENDMENTS.
  
 2- PLANS SUBMITTED DON'T HAVE THE ADDRESS OF THE
 BUILDING. SEC. 107.2.1 CITY AMENDMENTS.
  
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 PLEASE, INSERT CORRECTED PAGES INTO THE SUBMITTAL AND
 REMOVE/VOID THE PREVIOUSLY REVIEWED SHEETS.
 PLEASE DON'T STAPLE OLD DRAWINGS/DOCUMENTS . SUBMIT OLD
 DRAWINGS/DOCUMENTS FOR REFERENCE.
  