| 2019-05-02 12:01:07 | BUILDING REVIEW COMMENTS |
| | CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. |
| | |
| | NOTE: ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | SEC. 801.3 FBC-EXISTING BUILDING. |
| | |
| | 1- SCOPE OF WORK IS NOT CLEAR. PERMIT APPLICATION |
| | SPECIFIES "INSTALLATION OF NEW BOOSTER PUMP CONNECTING |
| | TO EXISTING BIOSOIDS PROJECT". PLANS SUBMITTED ARE ONLY |
| | ELECTRICAL PLANS. THEY DON'T SHOW WHAT IS NEW A WHAT IS |
| | NOT. WHERE IS THE NEW PUMP GOING TO BE INSTALLED. |
| | OUTSIDE? INSIDE?. ARE THERE ANY SPECIFICATIONS REQUIRED |
| | FOR ANCHORING THE NEW PUMP FOR WIND LOADS?. PROVIDE |
| | FLOOR PLANS SHOWING THE COMPLETE SCOPE OF WORK. SEC. |
| | 107.2.1 CITY AMENDMENTS. |
| | |
| | 2- PLANS SUBMITTED DON'T HAVE THE ADDRESS OF THE |
| | BUILDING. SEC. 107.2.1 CITY AMENDMENTS. |
| | |
| | |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | PLEASE, INSERT CORRECTED PAGES INTO THE SUBMITTAL AND |
| | REMOVE/VOID THE PREVIOUSLY REVIEWED SHEETS. |
| | PLEASE DON'T STAPLE OLD DRAWINGS/DOCUMENTS . SUBMIT OLD |
| | DRAWINGS/DOCUMENTS FOR REFERENCE. |
| | |