| 2019-04-17 08:46:12 | ****CORRECTIONS**** |
| | W.P.B. PERMIT: 19031158 |
| | REVIEWED: APRIL 17, 2019 |
| | |
| | DYLAN BATTLES |
| | BUILDING PLANS EXAMINER PX4191 |
| | [email protected] |
| | 561-805-6718 |
| | |
| | FBC[AMENDED] = FLORIDA BUILDING CODE,6TH EDITION (2017) |
| | FBC[B] = FBC BUILDING |
| | FBC[A] = FBC ACCESSIBILITY |
| | FBC[E] = FBC ENERGY CONSERVATION |
| | |
| | 1) 107.5.3 FBC[AMENDED] CODE EDITION. |
| | THIS PERMITTED UNDER FBC 2017 6TH EDITION. PLEASE |
| | UPDATE COVER SHEET WITH CODE VERSION APPLIED TO MAIN |
| | PERMIT 18081039. |
| | ALSO, VERIFY STRUCTURAL SHEET S-006 IS THE PAGE WITH |
| | WIND DESIGN CRITERIA. VERIFY IF DATA IS ON S-002 AND |
| | UPDATE COVER TO MATCH. |
| | |
| | 2) 107.3.4 FBC[AMENDED] THE REGISTERED DESIGN |
| | PROFESSIONAL IN RESPONSIBLE CHARGE SHALL BE RESPONSIBLE |
| | FOR REVIEWING AND COORDINATING SUBMITTAL DOCUMENTS |
| | PREPARED BY OTHERS, INCLUDING PHASED AND DEFERRED |
| | SUBMITTAL ITEMS, FOR COMPATIBILITY WITH THE DESIGN OF |
| | THE BUILDING. THOSE PRODUCTS WHICH ARE REGULATED BY FAC |
| | RULE 61G20 SHALL BE REVIEWED AND APPROVED IN WRITING BY |
| | THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| | JURISDICTIONAL APPROVAL. |
| | 107.3.4.1 FBC[AMENDED] DEFERRAL OF ANY SUBMITTAL ITEMS |
| | SHALL HAVE THE PRIOR APPROVAL OF THE BUILDING OFFICIAL. |
| | DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE |
| | SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL FOR |
| | REVIEW, AND THEN FORWARED TO THE BUILDING OFFICIAL |
| | INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE |
| | BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO |
| | THE DESIGN. THE DEFERRED SUBMITTAL ITEMS SHALL NOT BE |
| | INSTALLED UNTIL THE DEFERRED SUBMITTAL DOCUMENTS HAVE |
| | BEEN APPROVED BY THE BUILDING OFFICIAL. |
| | |
| | THE COVER SHEET REFERENCES THREE PRODUCT APPROVALS. |
| | FL14313.1-R9 |
| | FL20701.5-R2 |
| | FL180221.11 |
| | PLEASE PROVIDE TWO COPIES OF EACH WITH DESIGNER OF |
| | RECORD APPROVAL AND SELECTIONS MADE AS NEEDED. |
| | |
| | 3) 1709.5.1 AND 1709.5.1 FBC[B] HOW IS WATER |
| | INFILTRATION BEING HANDLED AT STOREFRONT ENTRY DOORS? |
| | |
| | |
| | |
| | NOTES: |
| | |
| | -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW |
| | EACH COMMENT IS BEING ADDRESSED. |
| | |
| | -COMMENTS ARE A BRIEF OVERVIEW OF CODE SECTIONS. |
| | FURTHER REVIEW OF THE REFERENCED CODE SECTIONS WILL BE |
| | REQUIRED. |
| | |
| | -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW |
| | OF MATERIALS REQUESTED. |
| | |
| | -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS |
| | OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS) |
| | SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT |
| | DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER |
| | SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID" |
| | OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS |
| | APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE |
| | NEED "VOID", RENDERING THEM NOT USABLE. |
| | |
| | PLEASE FEEL FREE TO CONTACT ME AT 561-805-6718 (M-F |
| | 8-5) TO DISCUSS COMMENTS, OR E-MAIL ANYTIME |
| | [email protected] |
| | |
| | |
| | |