| 2019-08-12 07:07:26 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | PROVIDE WRITTEN RESPONSE TO EACH PLAN REVIEW COMMENT |
| | |
| | 1. AS PER LAST PLAN REVIEW COMMENTS PROVIDE LOAD |
| | CALCULATIONS AND PANEL SCHEDULES FOR ALL NEW PANELS, |
| | ONLY LOAD CALCULATION PROVIDED WAS FOR NEW "CRITICAL |
| | LOAD PANEL" AND EXISTING SERVICE, NOTHING PROVIDED FOR |
| | NEW "MAIN PV PANEL" OR NEW "MAIN GENERATION PANEL" FBC |
| | 107.2.1 NEC 220 |
| | |
| | 2. DUE TO LINE SIDE TAP RUNNING AND EGC ALONG WITH THE |
| | GROUNDED CONDUCTOR TO PV AC DISCONNECT PROVIDES |
| | PARALLEL PATH TO GROUND. PROVIDE CORRECTION. |
| | |
| | 3. NO CUT SHEETS HAVE BEEN PROVIDED FOR NEW "BACK UP |
| | GATEWAY AUTOMATIC DISCONNECT" PROVIDE CUT SHEETS FOR |
| | PRODUCT APPROVAL SHOWING UL LISTING. FBC 107.2.1 NEC |
| | 90.7, 110.2, 110.3B |
| | |
| | 4. TESLA BATTER IS RATED FOR 30AMPS AND IS FEEDING |
| | "MAIN GENERATION PANEL" WITH #10'S AWG BUT CRITICAL |
| | LOAD PANEL IS BEING FED WITH #6'S AWG FROM "MAIN |
| | GENERATION PANEL"??? PROVIDE CORRECTION/ CLARIFICATION. |
| | FBC 107.2.1 |
| | |
| | |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | CODES IN EFFECT: |
| | |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE 2017 6TH ED. |
| | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| | 6TH EDITION |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |