| Plan Review Notes For Permit 19031098 |
| Permit Number |
19031098 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2019-08-27 11:30:34 | 1.) THE ENERGY REPORT IS LISTING AN ELECTRIC TANKLESS | | | WATER HEATER BUT THE PLAN IS SHOWING A GAS TANKLESS | | | WATER HEATER. CLARIFY. WPB AMEND TO FBC 107.2.1. 2ND | | | REQUEST. | | | 2.) THE WATER SUPPLY VALVES FOR THE STACKED | | | WASHER/DRYER SHALL BE ACCESSIBLE PER 2017 FBC-RES. SEC. | | | P2903.9.3. | | | 3) SHT.P1 - THE PLUMBING RISER SHOWS A LAUNDRY TUB BUT | | | IT IS NOT SHOWN ON THE FLOOR PLAN, CLARIFY. | | | 4) THE WASHING MACHINE STACK IS NOT SHOWN ON THE | | | PLUMBING RISER. WPB AMEN. TO FBC SEC. 107.2.1. | | | 5) THE WASHING MACHINE STACK SHALL BE A MINIMUM OF 3 | | | INCHES. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | |
|