2019-09-17 12:21:35CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1. PANEL SCHEDULES SHOW AN ELECTRICAL TANKLESS WATER
 HEATER, BUT THE PLAN SHOWS A GAS WATER HEATER. WHICH
 WILL BE USED? PROVIDE ACCURATE LOAD CALCULATION BASED
 ON THIS. NEC 220 FBC RE E3602.2 (LOAD CALCULATION STILL
 NOT CORRECT. IF THE WATER HEATER IS GAS, WHY DOES IT
 HAVE A 4500 VA LOAD ON A 30 AMP CIRCUIT? ALSO, SEE
 COMMENT 13 BELOW.)
 2. CORRECTED.
 3. PROVIDE COMPLIANCE: A MINIMUM OF 75 PERCENT OF THE
 LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF
 THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 CONTAIN ONLY HIGH EFFICACY LAMPS. A NOTE WILL SUFFICE.
 FBC EC C405.1, R404.1 (NOT PROVIDED.)
 4. CORRECTED.
 5. CORRECTED, NO FEED TO GUEST HOUSE SHOWN.
 6. CORRECTED, NO GUEST HOUSE SHOWN.
 7. CORRECTED, NO GUEST HOUSE SHOWN.
 8. PROVIDE SMOKE/CO ALARMS IN EACH LOCATION REQUIRED
 PER CODE. FBC RE R314.3, R315.1; WPB FBC 107.2.1 (SMOKE
 ALARMS MUST BE INSTALLED AT LEAST 3 FEET FROM BATHROOM
 DOOR, 3 FEET FROM CEILING FANS, AND 3 FEET FROM ANY
 MECHANICAL DUCT. PROVIDE CORRECTIONS. FBC RE R314.3(4),
 NFPA 72:29.8.3.4)
 9. SEVERAL AREAS DO NOT COMPLY WITH THE WALL SPACING
 REQUIREMENTS FOR OUTLETS. RECEPTACLES SHALL BE
 INSTALLED SO THAT NO POINT MEASURED HORIZONTALLY ALONG
 THE FLOOR LINE OF ANY WALL SPACE IS MORE THAN 6 FEET
 FROM A RECEPTACLE OUTLET. THE WALL SPACING REQUIREMENTS
 FOR KITCHEN COUNTER SPACE STATE THAT RECEPTACLE OUTLETS
 SHALL BE INSTALLED SO THAT NO POINT ALONG THE WALL LINE
 IS MORE THAN 24 INCHES MEASURED HORIZONTALLY FROM A
 RECEPTACLE OUTLET IN THAT SPACE. THE PLAN PROVIDED DOES
 NOT MEET THIS CODE IN SOME AREAS. PROVIDE CORRECTION.
 NEC 210.52(C)(1); FBC RE E3901 (NOT CORRECTED.)
 10. CORRECTED, NO GUEST HOUSE SHOWN.
 11. CORRECTED, NO GUEST HOUSE SHOWN.
 12. CORRECTED, NO GUEST HOUSE SHOWN.
  
 NEW COMMENTS:
  
 13. PROVIDE ACCURATE LOAD CALCULATION. NEW CALCULATION
 PROVIDED DID NOT INCLUDE THE RANGE, OR THE REQUIRED
 1500 VA FOR THE LAUNDRY CIRCUIT. NEC 220; FBC RE
 E3602.2
 14. PROVIDE CLARIFICATION. IS THERE NO MAIN HOUSE AND
 SEPARATE GUEST HOUSE NOW? THE PLAN SHOWS ONLY ONE
 STRUCTURE, WHAT HAPPENED TO THE LARGER STRUCTURE THAT
 WAS ON THE PREVIOUS PLANS? WPB FBC 107.2.1
 15. WHERE IS THE LOCATION OF THE AC EQUIPMENT? PROVIDE
 GFCI PROTECTED RECEPTACLE OUTLET FOR SERVICING OF A/C
 EQUIPMENT WITHIN 25 FEET OF THE EQUIPMENT PER CODE. NEC
 210.63; FBC RE E3901.12
 16. FOR A ONE FAMILY DWELLING AND EACH UNIT OF A
 TWO-FAMILY DWELLING THAT IS AT GRADE LEVEL, AT LEAST
 ONE RECEPTACLE OUTLET READILY ACCESSIBLE FROM GRADE AND
 NOT MORE THAN 2.0 M (6.5 FT) ABOVE GRADE LEVEL SHALL BE
 INSTALLED AT THE FRONT AND BACK OF THE DWELLING.
 PROVIDE CORRECTION. NEC 210.52(E)(1) FBC RE E3901.7
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  