| Plan Review Notes For Permit 19031098 |
| Permit Number |
19031098 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2019-04-09 13:59:13 | 1ST REVIEW: 19031092 | | | | | | 2017 FLORIDA BUILDING CODE 6TH EDITION | | | 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION | | | 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH | | | EDITION | | | 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION | | | 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION | | | 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH | | | EDITION | | | 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH | | | EDITION | | | | | | PLUMBING COMMENTS: | | | | | | 1. THE ENERGY REPORT IS LISTING AN ELECTRIC TANKLESS | | | WATER HEATER THE PLAN IS SHOWING A GAS TANKLESS WATER | | | HEATER PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1 | | | 2. ON THE GUEST HOUSE THE TANKLESS HEATER APPEARS TO BE | | | MOUNTED TO CLOSE TO THE WINDOW PROVIDE MANUFACTURE | | | INSTILLATION GUIDE TO DETERMINE EXACT DIMENSION. PER | | | WPB AMEND TO FBC 107.2.1 | | | 3. THE MAIN HOUSE SANITARY ISOMETRIC ON SHEET A5 ON THE | | | BATHROOM GROUP ONLY 1 FIXTURE IS ALLOWED TO DISCHARGE | | | UP STREAM OF THE WET VENT. PER FBC RES P3108.2.1 | | | 4. PLEASE SHOW THE SANITARY ISOMETRIC DRAWING ON THE | | | PLUMBING PAGE.PER WPB AMEND TO FBC 107.2.1 | | | | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561-805-6711 | | | [email protected] |
|