2019-04-09 13:55:391ST REVIEW: 19031092
  
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1. THE ENERGY REPORT IS LISTING AN ELECTRIC TANKLESS
 WATER HEATER THE PLAN IS SHOWING A GAS TANKLESS WATER
 HEATER PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1
 2. ON THE GUEST HOUSE THE TANKLESS HEATER APPEARS TO BE
 MOUNTED TO CLOSE TO THE WINDOW PROVIDE MANUFACTURE
 INSTILLATION GUIDE TO DETERMINE EXACT DIMENSION. PER
 WPB AMEND TO FBC 107.2.1
 3. THE MAIN HOUSE SANITARY ISOMETRIC ON SHEET A5 ON THE
 BATHROOM GROUP ONLY 1 FIXTURE IS ALLOWED TO DISCHARGE
 UP STREAM OF THE WET VENT. PER FBC RES P3108.2.1
 4. PLEASE SHOW THE SANITARY ISOMETRIC DRAWING ON THE
 PLUMBING PAGE.PER WPB AMEND TO FBC 107.2.1
  
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER