Plan Review Notes
Plan Review Notes For Permit 19031092
Permit Number 19031092
Review Stop M
Sequence Number 1
Notes
Date Text
2019-04-29 14:36:35MECHANICAL PLAN REVIER FAIL
  
 1- NEED ENERGY COMPLIANCE REPORT PER 2017 - FLORIDA
 BUILDING CODE - ENERGY CONSERVATION SEC R405.4.2.1
 COMPLIANCE REPORT FOR PERMIT APPLICATION.
 2- NEED MANUAL J PER 2017 - FLORIDA BUILDING CODE -
 ENERGY CONSERVATION SEC R403.7.1 EQUIPMENT SIZING.
  
 CHRIS MONTELLO
 561-805-6733