Plan Review Notes
Plan Review Notes For Permit 19031090
Permit Number 19031090
Review Stop E
Sequence Number 1
Notes
Date Text
2019-04-01 15:59:49ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 1) NEED TO SUBMIT CUT SHEETS FOR ALL FIXTURES AND
 ACCESSORIES.
  
 110.3 ( B) INSTALLATION AND USE. LISTED OR LABELED
 EQUIPMENT SHALL BE
 INSTALLED AND USED IN ACCORDANCE WITH ANY INSTRUCTIONS
 INCLUDED
 IN THE LISTING OR LABELING.
  
 410.6 LISTING REQUIRED ALL LUMINAIRES, LAMPHOLDERS, AND
 RETROFIT KITS SHALL BE LISTED.
  
  
 2) VALUE FOR WORK INVOLVED IS TO LOW, PLEASE SUBMIT A
 SIGNED CONTRACT FOR WORK.
  
 FBC 109.3 BUILDING PERMIT VALUATION. FOR PERMITTING
 PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE
 TOTAL REPLACEMENT
 VALUE TO INCLUDE STRUCTURAL, ELECTRIC, PLUMBING,
 MECHANICAL, INTERIOR FINISH, RELATIVE SITE WORK,
 ARCHITECTURAL AND DESIGN FEES,
 MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY
 LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST
 PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE
 CONGRESS. FINAL BUILDING PERMIT VALUATION SHALL BE SET
 BY THE BUILDING OFFICIAL.