| 2019-06-07 10:27:44 | PLAN REVIEW COMMENTS |
| | |
| | 2ND REVIEW: FBC FIFTH EDITION (2014) |
| | ROBERT MCDOUGAL, CBO |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561) 805-6714 |
| | [email protected] |
| | |
| | THE SUBMITTALS HAVE BEEN DENIED BY BUILDING |
| | PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| | |
| | 1) NOT ADDRESSED. THE BILCO ROOF HATCH, NOA NO |
| | 18-0226.04, HAS A MAXIMUM DESIGN PRESSURE OF +/- 70 |
| | PSF. THE ARCHITECTURAL AND STRUCTURAL ROOF PLANS SHOW |
| | THAT PART OF THE HATCH IS LOCATED IN ROOF ZONE 2 AND |
| | THE REST OF IT IS IN ROOF ZONE 1. THE REQUIRED NEGATIVE |
| | PRESSURE FOR ROOF ZONE 2 IS - 126.9 PSF AND FOR ROOF |
| | ZONE 1 IS -80.8 PSF , ACCORDING TO THE PRESSURES |
| | DETERMINED BY THE STRUCTURAL ENGINEER ON SHEET S0.4 OF |
| | THE PLANS. FBC 1609 AND 107.3.4 |
| | |
| | 2) NOT COMPLETELY ADDRESSED. THE NEW WINDOW/SLIDING |
| | GLASS DOOR AND AC ROOF STAND SUBMITTALS DO NOT HAVE THE |
| | DESIGNER OF RECORD'S SHOP REVIEW APPROVAL STAMP ON |
| | THEM. THE DESIGNER OF RECORD FOR THE BUILDING IS |
| | REQUIRED TO REVIEW AND APPROVE THE PRODUCT APPROVALS |
| | FOR THE EXTERIOR DOORS AND WINDOWS, AS WELL AS, THE |
| | SHOP DRAWINGS FROM THE SPECIALTY ENGINEER. FBC 107.3.4 |
| | & 107.3.4.1 |
| | |
| | 3) NOT ADDRESSED. THESE WERE NOT RESUBMITTED. THE |
| | SPECIALTY ENGINEER WHOSE NAME APPEARS IN THE TITLE |
| | BLOCK IS REQUIRED TO SIGN, SEAL AND DATE THE WINDOW |
| | WATERPROOFING DETAILS. 471.025, F.S., AND RULE |
| | 61G15-23.001, F.A.C. |
| | |
| | 4) COMPLIED. |
| | |
| | 5) COMPLIED. |
| | |
| | 6) COMPLIED. |
| | |
| | 7) COMPLIED. |
| | |
| | 8) COMPLIED. |
| | |
| | 9) WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A |
| | RESPONSE LETTER ADDRESSING EACH ITEM ALONG WITH THE |
| | CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS. |