2019-04-22 08:51:57PLUMBING 2ND REVIEW**DENIED**
  
  
 1) PLANS SHALL BE DRAWN UPON SUITABLE MATERIAL.
 DRAWINGS OR NOTES PROVIDE ON PLAN SHALL NOT BE IN
 PENCIL. FBC 107.2.1
  
 2) PROVIDE RAIN SENSOR ON PLAN. FS 373.82
  
 3) ZONE #2 SHOWS ALL PIPING 3/4" RUNNING 15 HEADS.
 PROVIDE DETAIL ON HEAD G.P.M, FLOW RATE FOR 3/4" PIPING
 WITH DESIGN PRESSURE AND PRESSURE LOSS THOUGH FITTINGS.
 FBC 107.3.5
  
 4) 2ND REQUEST. YOU AGAIN HAVE LISTED CITY WATER/ PUMP
 CITY WATER. PLEASE PROVIDE WHAT THE SOURCE OF WATER IS
 FOR THIS SYSTEM. FBC 107.3.5
  
  
 TIM HUNT
 PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR