| Plan Review Notes For Permit 19031039 |
| Permit Number |
19031039 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2019-04-22 08:51:57 | PLUMBING 2ND REVIEW**DENIED** | | | | | | | | | 1) PLANS SHALL BE DRAWN UPON SUITABLE MATERIAL. | | | DRAWINGS OR NOTES PROVIDE ON PLAN SHALL NOT BE IN | | | PENCIL. FBC 107.2.1 | | | | | | 2) PROVIDE RAIN SENSOR ON PLAN. FS 373.82 | | | | | | 3) ZONE #2 SHOWS ALL PIPING 3/4" RUNNING 15 HEADS. | | | PROVIDE DETAIL ON HEAD G.P.M, FLOW RATE FOR 3/4" PIPING | | | WITH DESIGN PRESSURE AND PRESSURE LOSS THOUGH FITTINGS. | | | FBC 107.3.5 | | | | | | 4) 2ND REQUEST. YOU AGAIN HAVE LISTED CITY WATER/ PUMP | | | CITY WATER. PLEASE PROVIDE WHAT THE SOURCE OF WATER IS | | | FOR THIS SYSTEM. FBC 107.3.5 | | | | | | | | | TIM HUNT | | | PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR | | | CITY OF WEST PALM BEACH | | | 561-248-2703 | | | [email protected] | | | [email protected] |
|