| Plan Review Notes For Permit 19031028 |
| Permit Number |
19031028 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2019-05-20 09:13:55 | BUILDING PLAN REVIEW | | | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | | | | JOSEAN A. DUPREY | | | BUILDING PLANS EXAMINER | | | CONSTRUCTION SERVICES DIVISION | | | TEL: 561-805-6716 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | 2ND REVIEW | | | RESULTS: DENIED | | | YOUR SUBMITTAL APPROVAL FOR THE SUBMITTED SCOPE OF WORK | | | IS PENDING DUE FOR THE REASONS LISTED BELOW. | | | | | | 1. PER PALM BEACH COUNTY PROPERTY APPRAISAL WEBSITE | | | THIS PROPERTY HAVE A TOTAL OF 2932 SQUARE FOOT. THE | | | ENERGY CALCULATIONS WERE SUBMITTED WITH A TOTAL OF 1818 | | | SQUARE FOOT AND A TOTAL OF 4 BEDROOMS, PLEASE CLARIFY. | | | ALSO THE LINE ITEM NUMER 9 IS ONLY INCLUDING ONE TYPE | | | OF WALL (CONCRETE BLOCK) WITH INSULATION TYPE R4.1, | | | HOWEVER THE DRAWING DETAIL 3/A2.0 SHOW AN INSULATION | | | TYPE R5 FOR THIS CONCRETE WALL TYPE. THE ENERGY | | | CALCULATION DOCUMENT DOES NOT SHOW INSULATION | | | REQUIREMENTS FOR UPPER FLOOR WOOD WALLS AS INDICATE ON | | | DETAIL 3/A2.0. PLEASE CLARIFY AND RE-SUBMIT. | | | | | | | | | |
|