| Date |
Text |
| 2019-04-29 13:49:49 | BUILDING PLAN REVIEW |
| | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1 ADMINISTRATION |
| | |
| | CHRISTOPHER S. THROOP, C.B.O. |
| | BUILDING PLANS EXAMINER, PX3169 |
| | 1&2 FAMILY PLANS EXAMINER, SFP306 |
| | CONSTRUCTION SERVICES DIVISION |
| | TEL: 561-805-6726 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | 1ST REVIEW |
| | RESULTS: DENIED |
| | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED |
| | BELOW. |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | |
| | 1. DESIGN PROFESSIONALS SIGNATURE AND SEAL IS INVALID. |
| | |
| | PLANS THAT HAVE BEEN PREPARED BY AN ENGINEER AND |
| | SUBMITTED FOR PUBLIC RECORD SHALL BEAR THE SIGNATURE, |
| | DATE AND SEAL OF THE ENGINEER PER FL ADMIN. CODE RULE |
| | 61G15-23.001. |
| | |
| | DOCUMENTS PREPARED BY AN ENGINEER AND SUBMITTED FOR |
| | PUBLIC RECORD ARE TO BE SIGNED, SEALED, DATED ORIGINALS |
| | FS471. A PHOTOCOPY SIGNATURE IS NOT ACCEPTABLE TO FBPE. |
| | |
| | 2. ROOFING PERMIT REQUIRED. |
| | FBC 107.3.4 ? PROVIDE PRODUCT APPROVALS FOR THOSE |
| | PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED |
| | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. |
| | SPECIFICALLY, PROVIDE ROOFING SUBMITTALS. |
| | |
| | 3. PROVIDE PRODUCT APPROVAL FOR NEW FRENCH DOORS. |
| | INSTALLATION INSTRUCTIONS REQUIRED. |
| | |
| | 4. WINDOW NOT PERMITTED ON ZERO LOT LINE UNLESS THE |
| | FOLLOWING CONDITION APPLIES. IF THIS EXCEPTION IS USED, |
| | PROVIDE SITE PLAN SHOWING DISTANCE TO ADJOINING |
| | STRUCTURE. |
| | FOR ZERO LOT LINE DEVELOPMENTS WHERE PERMITTED BY LOCAL |
| | REGULATIONS, OPENINGS AND ROOF OVERHANG PROJECTIONS |
| | SHALL BE PERMITTED ON THE EXTERIOR WALL OF A BUILDING |
| | LOCATED ON A ZERO LOT LINE WHEN THE BUILDING EXTERIOR |
| | WALL IS SEPARATED FROM AN ADJACENT BUILDING EXTERIOR |
| | WALL BY A DISTANCE OF 6 FEET OR MORE, AND THE ROOF |
| | OVERHANG PROJECTION IS SEPARATED FROM AN ADJACENT |
| | BUILDING PROJECTION BY A DISTANCE OF 4 FEET OR MORE, |
| | WITH 1-HOUR FIRE-RESISTIVE CONSTRUCTION ON THE |
| | UNDERSIDE OF THE OVERHANG REQUIRED, UNLESS THE |
| | SEPARATION BETWEEN PROJECTIONS IS 6 FEET OR MORE. |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY |
| | REVIEWED SHEETS DETACHED. |
| | |
| | |
| | |
| | |
| | |
| | |