| 2019-04-16 08:21:05 | FLORIDA BUILDING CODE 2017 6TH EDITION |
| | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED |
| | NFPA 70 2014 EDITION |
| | |
| | JAKE LEAHY |
| | ELECTRICAL PLANS EXAMINER II |
| | 561-805-6713 |
| | [email protected] |
| | |
| | |
| | 1) DISCONNECT REQUIRED FOR SEPARATE STRUCTURE |
| | |
| | 225.30 NUMBER OF SUPPLIES |
| | A BUILDING OR OTHER STRUCTURE THAT IS SERVED BY A |
| | BRANCH CIRCUIT OR |
| | FEEDER ON THE LOAD SIDE OF A SERVICE DISCONNECTING |
| | MEANS SHALL BE |
| | SUPPLIED BY ONLY ONE FEEDER OR BRANCH CIRCUIT UNLESS |
| | PERMITTED IN |
| | 225.30(A) THROUGH (E). FOR THE PURPOSE OF THIS SECTION, |
| | A MULTIWIRE |
| | BRANCH CIRCUIT SHALL BE CONSIDERED A SINGLE CIRCUIT. |
| | WHERE A BRANCH CIRCUIT OR FEEDER ORIGINATES IN THESE |
| | ADDITIONAL |
| | BUILDINGS OR OTHER STRUCTURES, ONLY ONE FEEDER OR |
| | BRANCH CIRCUIT |
| | SHALL BE PERMITTED TO SUPPLY POWER BACK TO THE ORIGINAL |
| | BUILDING |
| | OR STRUCTURE, UNLESS PERMITTED IN 225.30(A) THROUGH |
| | (E). |
| | |
| | |
| | 2) SEPARATE GROUNDING ELECTRODE SYSTEM REQUIRED. |
| | |
| | 250.32 BUILDINGS OR STRUCTURES SUPPLIED |
| | BY A FEEDER(S) OR BRANCH CIRCUIT(S) |
| | (A) GROUNDING ELECTRODE. BUILDING(S) OR STRUCTURE(S) |
| | SUPPLIED |
| | BY FEEDER(S) OR BRANCH CIRCUIT(S) SHALL HAVE A |
| | GROUNDING ELECTRODE |
| | OR GROUNDING ELECTRODE SYSTEM INSTALLED IN ACCORDANCE |
| | WI TH |
| | PART III OF ARTICLE 250. THE GROUNDING ELECTRODE |
| | CONDUCTOR(S) SHALL |
| | BE CON NECTED IN ACCORDANCE WITH 250.32(B) OR (C). |
| | WHERE THERE |
| | IS NO EXISTING GROUNDING ELECTRODE, THE GROUNDING |
| | ELECTRODE(S) |
| | REQUIRED IN 250.50 SHALL BE INSTALLED. |
| | |
| | 3) VALUE FOR WORK SEEMS LOW PLEASE SUBMIT A SIGNED |
| | CONTRACT FOR WORK INVOLVOED. |