Plan Review Notes
Plan Review Notes For Permit 19030978
Permit Number 19030978
Review Stop B
Sequence Number 1
Notes
Date Text
2019-03-21 16:04:16BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 JOSEAN A. DUPREY E.I.
 BUILDING PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6716
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. THE FOUNDATION DEPTH ON THE DRAWINGS IS 6 INCHES
 FROM GRADE LEVEL, PER FBC 1809.4 IT SHALL BE 12 INCHES.
 PLEASE REVISED AND RE-SUBMIT.
  
 1809.4 DEPTH AND WIDTH OF FOOTINGS.
 THE MINIMUM DEPTH OF FOOTINGS BELOW THE UNDISTURBED
 GROUND SURFACE SHALL BE 12 INCHES (305 MM). WHERE
 APPLICABLE, THE REQUIREMENTS OF SECTION 1809.5 SHALL
 ALSO BE SATISFIED. THE MINIMUM WIDTH OF FOOTINGS SHALL
 BE 12 INCHES (305 MM).
  
  