| Plan Review Notes For Permit 19030972 |
| Permit Number |
19030972 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2019-06-06 17:24:24 | BUILDING REVIEW APPROVED WITH PROVISO: | | | | | | 1- SPECIFY ALL STRUCTURAL CONNECTORS FOR ALL INFILL | | | EXTERIOR WALLS IN NEW KITCHEN. | | | 2- PROVIDE PRODUCT APPROVAL (2 COPIES) FOR: | | | A) SINGLE HUNG WINDOW SIZE (5'-2"WIDTH X 4'-6" HEIGHT ) | | | SPECIFIED ON THE WINDOW SCHEDULE FOR WINDOW W-112. | | | B) WINDOW MULLIONS (IF USED) PLANS ARE NOT CLEAR. AND, | | | CLEARLY SPECIF MULLION SIZE TO VERIFY COMPLIANCE WITH | | | THE CALCULATED DESIGN PRESSURES. | | | C) FRONT DOOR PRODUCT APPROVAL SUBMITTED IS INCOMPLETE. | | | NEED TO PROVIDE COMPLETE FLORIDA PRODUCT APPROVAL (2 | | | COPIES), INCLUDING THE FLORIDA PRODUCT APPROVAL COVER | | | PAGE THAT CORRESPONDS TO THE DRAWINGS SUBMITTED. THE | | | FLORIDA PRODUCT APPROVAL IS REQUIRED BECAUSE IT SHOWS | | | IF PRODUCT IS APPROVED AND CURRENT CODE IN EFFECT. | | | 3- DESIGNER OF RECORD TO APPROVE ALL PRODUCT APPROVALS. |
|