2019-12-31 14:58:37CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1. CORRECTED.
 2. PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE
 EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE
 IS ADEQUATE. NEC 215.2, 220, 408.30 (LOAD CALCULATION
 PROVIDED IS NOT PER CODE. IF THE EXISTING LOAD IS TO BE
 DETERMINED BASED ON DEMAND, ALL OF THE ITEMS IN NEC
 220.87 ARE REQUIRED. ADDITIONALLY, THE SHEET THAT SHOWS
 THE LOAD CALCULATION IS NOT SIGNED BY THE PERSON
 RESPONSIBLE FOR THE DESIGN. PROVIDE CORRECTIONS.)(3RD
 REVIEW: PER 220.87, THE LOAD MUST BE CALCULATED AT THE
 MAXIMUM DEMAND PLUS 25%, PLUS THE NEW LOAD.
 ADDITIONALLY, PROOF OF THE MAXIMUM DEMAND MUST BE
 SUBMITTED. PROVIDE CORRECTION.)
 3. CORRECTED.
 4. CORRECTED.
  
 NEW COMMENT:
  
 5. RISER DIAGRAM SUPPLIED ON NEW PLAN DOES NOT STATE
 THE SIZE OF THE ELECTRICAL SERVICE. WHAT IS THE
 AMPERAGE RATING OF THIS SERVICE? NEC 215.5; WPB FBC
 107.2.1
  
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  