| 2019-09-11 11:54:16 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | FAC = FLORIDA ADMINISTRATIVE CODE |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED |
| | SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS |
| | COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY |
| | HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW |
| | COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS. |
| | |
| | 1. CORRECTED. |
| | 2. PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE |
| | EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE |
| | IS ADEQUATE. NEC 215.2, 220, 408.30 (LOAD CALCULATION |
| | PROVIDED IS NOT PER CODE. IF THE EXISTING LOAD IS TO BE |
| | DETERMINED BASED ON DEMAND, ALL OF THE ITEMS IN NEC |
| | 220.87 ARE REQUIRED. ADDITIONALLY, THE SHEET THAT SHOWS |
| | THE LOAD CALCULATION IS NOT SIGNED BY THE PERSON |
| | RESPONSIBLE FOR THE DESIGN. PROVIDE CORRECTIONS.) |
| | 3. SIGNATURE. PER THE WPB AMENDMENTS TO THE FBC, PLAN |
| | (EACH SHEET OF BOTH COPIES) IS REQUIRED TO BEAR THE |
| | NAME AND BE SIGNED AND SEALED BY A DESIGN PROFESSIONAL |
| | OR SIGNED BY THE ELECTRICAL CONTRACTOR QUALIFIER. |
| | PROVIDE CORRECTION. WPB FBC 107.1, 107.2; FS 471, 481 |
| | |
| | NEW COMMENT: |
| | |
| | 4. PER THE WPB AMENDMENTS TO THE FBC, SUBMITTAL |
| | DOCUMENTS CONSISTING OF CONSTRUCTION DOCUMENTS, |
| | STATEMENT OF SPECIAL INSPECTIONS, GEOTECHNICAL REPORT |
| | AND OTHER DATA SHALL BE SUBMITTED IN TWO OR MORE SETS |
| | WITH EACH PERMIT APPLICATION. THE SUBMISSION PROVIDED |
| | IS NOT IN TWO COMPLETE SETS, THERE IS INFORMATION |
| | SCATTERED THROUGHOUT THE PACKAGE. PROVIDE TWO COMPLETE |
| | SETS WITH ALL RELATED INFORMATION FOR THE PROJECT. WPB |
| | FBC 107.1 |
| | |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY |
| | REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED |
| | SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD |
| | SHEETS. |
| | |
| | SINCERELY, |
| | |
| | JOHN PEARSON |
| | ELECTRICAL PLANS EXAMINER |
| | 561-805-6746 |
| | [email protected] |
| | |