| 2019-04-09 13:03:52 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | FAC = FLORIDA ADMINISTRATIVE CODE |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. PROVIDE GFCI PROTECTED RECEPTACLE OUTLET FOR |
| | SERVICING OF A/C EQUIPMENT WITHIN 25 FEET OF THE |
| | EQUIPMENT PER CODE. NEC 210.63 |
| | 2. PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE |
| | EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE |
| | IS ADEQUATE. NEC 215.2, 220, 408.30 |
| | 3. PROVIDE CORRECTION FOR ENGINEERS SIGNATURE. PER FAC |
| | 61G15-23.003 PROCEDURES FOR PHYSICALLY SIGNING AND |
| | SEALING PLANS, SPECIFICATIONS, REPORTS OR OTHER |
| | DOCUMENTS. |
| | ENGINEERING PLANS, SPECIFICATIONS, REPORTS OR OTHER |
| | DOCUMENTS WHICH MUST BE SIGNED, DATED AND SEALED IN |
| | ACCORDANCE WITH THE PROVISIONS OF SECTION 471.025, |
| | F.S., AND RULE 61G15-23.001, F.A.C. MAY BE PHYSICALLY |
| | SIGNED, DATED AND SEALED AS PROVIDED HEREIN BY THE |
| | PROFESSIONAL ENGINEER IN RESPONSIBLE CHARGE. |
| | (1) THE LICENSEE SHALL SIGN BY HAND AN ORIGINAL OF THE |
| | LICENSEE?S SIGNATURE ON EACH PAGE REQUIRED TO BE |
| | SEALED. A SCANNED, FACSIMILE, DIGITALLY CREATED OR |
| | COPIED IMAGE OF THE LICENSEE?S SIGNATURE SHALL NOT BE |
| | USED. |
| | (2) THE LICENSEE MUST THEN USE A WET SEAL, A DIGITALLY |
| | CREATED SEAL, OR AN EMBOSSING SEAL PLACED PARTIALLY |
| | OVERLAPPING THE LICENSEE?S SIGNATURE ON EACH PAGE |
| | REQUIRED TO BE SEALED. THE PLACEMENT OF THE SEAL SHALL |
| | NOT RENDER THE SIGNATURE ILLEGIBLE. |
| | |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY |
| | REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED |
| | SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD |
| | SHEETS. |
| | |
| | SINCERELY, |
| | |