Plan Review Notes
Plan Review Notes For Permit 19030941
Permit Number 19030941
Review Stop P
Sequence Number 2
Notes
Date Text
2019-08-12 08:49:281) SUBMIT TWO COPIES OF THE UL 142 CERTIFICATION FOR
 THE FUEL TANK.WPB AMEND. TO FBC SEC. 107.2.1. THE
 RESPONSE STATES "WILL COMPY." WHEN? THE DOCUMENT IS
 REQUIRED TO BE SUBMITTED AT THIS TIME. 2ND REQUEST.
 2) SUBMIT TWO COPIES OF THE APPROVAL FROM THE PALM
 BEACH COUNTY DEPARTMENT OF ENVIRONMENTAL RESOURCE
 MANAGEMENT FOR THE FUEL TANK AND COMPLIANCE WITH PALM
 BEACH COUNTY ORDINANCE 2015-008. THIS DOCUMENT IS
 REQUIRED TO BE SUBMITTED AT THIS TIME. 2ND REQUEST.
 3) SUBMIT DETAILS AS TO HOW THE GENERATOR IS PROTECTED
 AGAINST UNAUTHORIZED ACCESS, TAMPERING AND TRESPASSING.
 NFPA 30 SEC. 15.3.6, WPB AMEND. TO FBC SEC. 107.2.1. IS
 THE GENERATOR SURROUNDED BY A LOCKED CHAIN LINK FENCE.
 BE SPECIFIC AND NOTE ON THE PLAN.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  